Plan Review Notes
Plan Review Notes For Permit 12090498
Permit Number 12090498
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-09-25 10:54:492275 PALM BEACH LAKES BOULEVARD
 PERMIT #12090498
 MASTER #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPRINKLER PLANS
 THE SPRINKLER PLANS AND HYDRAULIC CALCULATIONS ARE NOT
 SIGNED AND SEALED BY THE PROFESSIONAL ENGINEER (B.
 MASKOL).
  
 PLEASE PROVIDE HYDRAULIC CALCULATIONS FOR THE SOUTHWEST
 (CLASSROOM AREA) OF THE BUILDING (ROOM #105A & #105B).
  
  
 CIVIL PLANS
 METRO FIRE SPRINKLER HAS INDICATED THAT THEIR SCOPE OF
 WORK BEGINS AT 1'-0" ABOVE FINISHED FLOOR; THEREFORE A
 SEPARATE PLAN AND PERMIT WILL BE NEEDED FOR THE
 UNDERGROUND FIRE SERVICE MAIN.
  
 A FIRE HYDRANT IS NEEDED WITHIN 150 FEET OF THE FIRE
 DEPARTMENT CONNECTION.
  
 **FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF
 7?-6? TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE PER
 SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. THESE
 CLEARANCES WILL AFFECT THE ADJACENT PARKING SPACES.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  