Plan Review Notes For Permit 12090498 |
Permit Number |
12090498 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-09-25 10:54:49 | 2275 PALM BEACH LAKES BOULEVARD | | PERMIT #12090498 | | MASTER #12030334 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SPRINKLER PLANS | | THE SPRINKLER PLANS AND HYDRAULIC CALCULATIONS ARE NOT | | SIGNED AND SEALED BY THE PROFESSIONAL ENGINEER (B. | | MASKOL). | | | | PLEASE PROVIDE HYDRAULIC CALCULATIONS FOR THE SOUTHWEST | | (CLASSROOM AREA) OF THE BUILDING (ROOM #105A & #105B). | | | | | | CIVIL PLANS | | METRO FIRE SPRINKLER HAS INDICATED THAT THEIR SCOPE OF | | WORK BEGINS AT 1'-0" ABOVE FINISHED FLOOR; THEREFORE A | | SEPARATE PLAN AND PERMIT WILL BE NEEDED FOR THE | | UNDERGROUND FIRE SERVICE MAIN. | | | | A FIRE HYDRANT IS NEEDED WITHIN 150 FEET OF THE FIRE | | DEPARTMENT CONNECTION. | | | | **FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF | | 7?-6? TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE PER | | SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. THESE | | CLEARANCES WILL AFFECT THE ADJACENT PARKING SPACES. | | | | PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR | | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | POSITION. | | | | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | CONNECTION. | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | DEPARTMENT CONNECTION. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | | 2012-09-20 13:54:00 | WITH FIRE DD |
|