Plan Review Notes
Plan Review Notes For Permit 12090495
Permit Number 12090495
Review Stop B
Sequence Number 1
Notes
Date Text
2012-09-20 10:32:06RESIDENTIAL (R3) ROOFING REVISION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO THE PROPERTY APPRAISER WEBSITE THIS
 PROPERTY IMPROVEMENT VALUE IS $19,146. THIS PROPERTY IS
 LOCATED ON FLOOD ZONE A7. ACCORDING TO THE CITY CODE
 THE PROPERTY NEEDS TO BE 6" ABOVE THE BASE FLOOD
 ELEVATION. SEC. 94-546(A)(3) AND SEC. 94-546(B)(1) OF
 CITY CODE. PROVIDE COPY OF FLOOD ELEVATION CERTIFICATE
 OR SURVEY SHOWING THE FINISH FLOOR ELEVATION OF THE
 HOUSE. IF THE HOUSE FINISH FLOOR ELEVATION IS LESS THAN
 7'-6", THEN, THE HOUSE NEEDS TO BE RAISED TO COMPLY.
  
 2- BORAL ROOFING UNDERLAYMENT FL14317-R2 SUBMITTED:
 ACCORDING TO LIMITATION #5.5.2.1 THE MAXIMUM DESIGN
 PRESSURE FOR THIS UNDERLAYMENT IS -45PSF. THIS HOUSE IS
 LOCATED ON EXPOSURE "D" AND THE DESIGN PRESSURES ARE
 HIGHER THAN -45PSF. THEREFORE, THIS PRODUCT APPROVAL
 CAN'T BE USED. PROVIDE OTHER PRODUCT APPROVAL THAT
 MEETS THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712