2012-09-14 10:54:51 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- FLAT ROOF: | | A) SPECIFY WHICH APPROVED ASSEMBLY FROM NOA 12-0227.18 | | SUBMITED IS GOING TO BE USED TO VERIFY COMPLIANCE WITH | | THE DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF | | 2010 FLORIDA RESIDENTIAL CODE. | | | | B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 TO MEET THE DESIGN PRESSURES REQUIRED BY | | SEC. R301.2.1.4.3. | | | | 2- ALUMINUM SKYLIGHT NOA 08-0611.09 SUBMITTED WAS | | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE | | AND DOWNLOAD CURRENT NOA. SUBMITT TWO NEW COPIES. SEC. | | 107.2.1.2 CITY AMENDMENTS TO FBC AND DCA RULE 9N-3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|