Plan Review Notes For Permit 12090294 |
Permit Number |
12090294 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-09-18 13:59:51 | BUILDING PROVISO: | | 2010 FBC-B 907.2.13 HIGH-RISE BUILDINGS | | | | 907.2.13.1.1 AREA SMOKE DETECTION. [F] | | | | AREA SMOKE DETECTORS SHALL BE PROVIDED IN ACCORDANCE | | WITH THIS SECTION. SMOKE DETECTORS SHALL BE CONNECTED | | TO AN AUTOMATIC FIRE ALARM SYSTEM. THE ACTIVATION OF | | ANY DETECTOR REQUIRED BY THIS SECTION SHALL OPERATE THE | | EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN | | ACCORDANCE WITH SECTION 907.5.2.2. SMOKE DETECTORS | | SHALL BE LOCATED AS FOLLOWS: | | 2. IN EACH ELEVATOR MACHINE ROOM AND IN ELEVATOR | | LOBBIES. | | | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|