2012-09-13 10:29:16ROOF-RECOVER BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED
 ON EXPOSURE "C" NOT EXPOSURE "B". ENGINEER NEEDS TO
 REVISE THE ROOF COMPONENTS AND CLADDING CALCULATIONS
 AND THE RAS 117 CALCULATIONS AS REQUIRED.
  
 2- ENGINEER CALCULATIONS SUBMITTED SPECIFY ROOF
 COMPONENTS AND CLADDING FOR GABLE/HIP ROOFS. THIS
 BUILDING HAS A LOW SLOPE ROOF. CLARIFY AND REVISE AS
 REQUIRED. SEC. 107.2.1.2 CITY AMENDMENTS TO FBC.
  