2012-10-16 16:54:27 | 2010 FBC & 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) PROVIDE ELECTRICAL RISER DIAGRAMS WITH WIRE SIZES, | | CONDUIT DETAIL AND GROUNDING DETAIL ON THE PLANS FOR | | BUILDING A & BUILDING B. CITY AMENDMENTS FBC 107.3.5.3 | | | | 2) THE OVERHEAD GARAGE DOOR RECEPTACLE FOR THE LEFT | | UNIT ON SHEET E-1 OF BUILDING B IS NOT SPECIFIED AS | | GFCI. NEC 210.8 | | | | 3) REVISE THE NOTE FOR AFCI PROTECTION IN THE | | ELECTRICAL LEGEND TO INCLUDE IN ADDITION TO BEDROOMS | | THE OTHER ROOMS LISTED IN NEC 210.12(B). | | | | 4) CORRECT THE NOTE BELOW THE LOAD CALCULATIONS ON | | SHEET E2 OF BUILDING A THAT REFERENCES THE 2005 NEC. | | THE CURRENT EDITION IS 2008 NEC. | | | | 5) THE LIGHT AND RECEPTACLE AT THE ATTIC ACCESS IS | | SHOWN IN THE WRONG CLOSETS ON SHEET E2 OF BUILDING A. | | NEC 210.70 (3) | | | | 6) THERE ARE REVISION NOTES IN THE TITLE BLOCK FROM | | 2009 ON SHEETS E1 OF BUILDING A & E2 OF BUILDING B. | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|