2012-10-17 15:27:49 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD OF THE PROJECT PER |
| CITY AMENDMENTS 107.3.4.1 |
| |
| 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 8" |
| LINTELS. DCA RULE 9N-3 |
| |
| 3) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE |
| DEMILEC SPRAY FOAM INSULATION. FBC R316 |
| |
| 4) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE |
| HUBER ROOF SHEATHING SYSTEM. FBC R803 AND CITY |
| AMENDMENTS 107.2.1.3 |
| |
| 5) ON SHEET T-1 FOR BUILDING A, UNDER THE PROJECT |
| ANALYSIS EXPOSURE B IS SPECIFIED RATHER THAN C. FBC |
| R301.2.1.4 |
| |
| 6) ON SHEET A-2 BLDG. A, THERE IS A DETAIL TAG FOR 2 ON |
| A3.2 AT THE LAUNDRY ROOM THAT APPEARS TO BE A TYPO. |
| PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| |
| 7) ON A-4 FOR BLDG. A, THE LEFT SIDE ELEVATION IS |
| MIS-LABELED AS RIGHT SIDE ELEVATION. CITY AMENDMENTS |
| 107.2.1 |
| |
| 8) ON SHEET A-6 BLDG. A, THERE IS A REVISION DATED |
| 8/31/11 IN THE TITLE BLOCK. PLEASE CORRECT. CITY |
| AMENDMENTS 107.2.1 |
| |
| 9) ON SHEETS A-1 AND A-2, BOTH BUILDING TYPES HAVE NOTE |
| 2 ON THE DOOR SCHEDULE THAT REFERENCES THE 2011 FBC. |
| PLEASE CORRECT TO THE 2010 FBC. |
| |
| 10) THE FLOOR PLANS ON SHEETS A-1 AND A-2 FOR BUILDING |
| B ARE MISSING THE DIMENSION LINES. PLEASE CORRECT. CITY |
| AMENDMENTS 107.2.1 |
| |
| 11) SHEET A-2 BLDG. B HAS REVISIONS FROM 2009 NOTED IN |
| THE TITLE BLOCK. PLEASE CHECK ALL SHEETS FOR OLD |
| REVISIONS NOTES THAT DO NOT PERTAIN TO THIS PERMIT AND |
| REMOVE THEM. CITY AMENDMENTS 107.2.1 AND FS 481 |
| |
| 12) ON SHEET A-4A BLDG. B THE LEFT ELEVATION IS NOT |
| LABELED AND THERE IS A TYPO WHERE THE FLOOR/BEAM |
| ELEVATIONS ARE PRINTED OVER THE TITLE BLOCK. PLEASE |
| CORRECT. CITY AMENDMENTS 107.2.1 |
| |