Date |
Text |
2012-12-10 11:26:55 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 1. THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD ZONE |
| A8. WPB MUNICIPAL CODE 94 546(B), ALL NEW IMPROVEMENTS |
| TO COMPLY WITH REQUIREMENTS FOR NEW CONSTRUCTION. |
| FINISHED FLOOR SLAB TO BE AT A MINIMUM OF 16.5 FT. THE |
| GRADING PLAN AND OTHER SHEETS SHOW A BUILDING ELEVATION |
| OF 20.40 FT. PROPOSED CONSTRUCTION APPEARS TO COMPLY; |
| PLEASE PROVIDE A SIGNED AND SEALED ELEVATION |
| CERTIFICATE (CONSTRUCTION DRAWINGS). AN ADDITIONAL |
| ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO C.O. |
| (FINAL CONSTRUCTION). THE ELEVATION CERTIFICATE CAN BE |
| EITHER THE FEMA 2009 ELEVATION CERTIFICATE FORM (OMB |
| NO. 1660-0008, EXPIRES MARCH 31, 2012) OR ON THE NEW |
| FORM WHICH WILL BE AVAILABLE NEXT WEEK ON THE FEMA |
| WEBSITE. THERE WILL BE A ONE YEAR PHASE IN PERIOD |
| DURING WHICH THE NEW FORM WILL BE VOLUNTARY. |
| |
| 2ND REVIEW, PLEASE PROVIDE ELEVATION CERTIFICATE |
| (CONSTRUCTION DRAWINGS) AS REQUESTED. INFORMATION SUCH |
| AS PROPOSED ELEVATION, MECHANICAL EQUIPMENT ELEVATION, |
| AND OTHER ITEMS WILL BE REVIEWED. |
| |
| 2. LS 1.0, ARRANGEMENTS OF EXITS, SEE FBC 1015.2.1, |
| EXIT DOORS TO BE PLACED A DISTANCE APART EQUAL TO NOT |
| LESS THAN ONE HALF OF THE LENGTH OF THE MAXIMUM OVERALL |
| DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED |
| (ONE THIRD DISTANCE IF BUILDING IS SPRINKLERED, SEE |
| EXCEPTION). |
| |
| PLEASE REVISE NOTE (WHICH STATES 1/3 DIAGONAL) AND |
| DIMENSIONS AS REQUIRED. |
| |
| 3. OK. |
| |
| 4. LS 1.0, TRAVEL DISTANCE OF 114 FT 4 IN SHOWN FROM |
| ONE CORNER TO OPPOSITE EXIT. PLEASE ALSO SHOW COMMON |
| PATH AS IT APPEARS TO EXCEED 75 FEET, FBC 1014.3. |
| |
| 2ND REVIEW, PLEASE REVISE TO SHOW COMMON PATH AS |
| DEFINED BY FBC 1002: |
| |
| "THAT PORTION OF EXIT ACCESS WHICH THE OCCUPANTS ARE |
| REQUIRED TO TRAVERSE BEFORE TWO SEPARATE AND DISTINCT |
| PATHS OF EGRESS TRAVEL TO TWO EXITS ARE AVAILABLE" (NOT |
| VISIBLE AS STATED ON PLAN). PLEASE CONTACT ME IF YOU |
| WISH TO DISCUSS. |
| |
| 5. OK |
| |
| 6. NOTE THE FOLLOWING REGARDING PRODUCT APPROVALS |
| FAC9N-3, FBC 1609: |
| |
| AC STAND - IF MANUFACTURED ONSITE, PROVIDE A DETAIL. IF |
| MANUFACTURED OFF SITE, FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL REQUIRED |
| |
| ALUMINUM IMPACT BI PARTING CAR DOOR SYSTEM - PROVIDE |
| PRODUCT APPROVAL TO VERIFY DESIGN PRESSURES, IMPACT, |
| AND METHOD OF INSTALLATION. THIS MAY HAVE BEEN PROVIDED |
| TO YOU WITH THE RECORDS RESEARCH REQUEST INFORMATION. |
| |
| PAIR 4X8 IMPACT STOREFRONT DOOR SYSTEM (DOOR A) - OK |
| |
| WINDOW WALL SYSTEM WITH DOOR (DOOR B) - OK |
| |
| IMPACT SINGLE DOOR (DOOR C) - OK |
| |
| ROOF - ULTRAGARD PVC SR 50 - THE ASSEMBLY SELECTED IS |
| FOR WOOD DECK, PLAN SHOWS DOUBLE TEES. ENGINEERING |
| REQUIRED FOR ZONES 2 AND 3 IF ASSEMBLY DESIGN PRESSURE |
| DOES NOT MEET MINIMUMS SPECIFIED BY ENGINEER. |
| |
| NEW EIFS WALL SYSTEM - OK |
| |
| BUTT GLAZED WINDOW WALL SYSTEM (PRODUCT APPROVAL OR |
| TEST REPORT AS PER A 5.0) - OK |
| |
| ANY INFORMATION NOT SUBMITTED PRIOR TO PERMIT ISSUANCE |
| WILL BE REQUIRED TO BE SUBMITTED AS A REVISION. DESIGN |
| PRESSURES TO MEET REQUIREMENTS ON S 7.1. |
| |
| 7. OK. |
| |
| 8. PLEASE PROVIDE THE ENERGY CALCS. THE DOCUMENT WHICH |
| WAS UPLOADED WHICH IS NAMED LOADENERGYCALCULATIONS.PDF |
| IS THE SAME DOCUMENT AS THE CIVIL COST ESTIMATE. SEE |
| FBC 2010 ENERGY 103.2.3. |
| |
| 9. OK. |
| |
| 10. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY |
| REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| |