2012-12-10 11:26:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD ZONE
 A8. WPB MUNICIPAL CODE 94 546(B), ALL NEW IMPROVEMENTS
 TO COMPLY WITH REQUIREMENTS FOR NEW CONSTRUCTION.
 FINISHED FLOOR SLAB TO BE AT A MINIMUM OF 16.5 FT. THE
 GRADING PLAN AND OTHER SHEETS SHOW A BUILDING ELEVATION
 OF 20.40 FT. PROPOSED CONSTRUCTION APPEARS TO COMPLY;
 PLEASE PROVIDE A SIGNED AND SEALED ELEVATION
 CERTIFICATE (CONSTRUCTION DRAWINGS). AN ADDITIONAL
 ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO C.O.
 (FINAL CONSTRUCTION). THE ELEVATION CERTIFICATE CAN BE
 EITHER THE FEMA 2009 ELEVATION CERTIFICATE FORM (OMB
 NO. 1660-0008, EXPIRES MARCH 31, 2012) OR ON THE NEW
 FORM WHICH WILL BE AVAILABLE NEXT WEEK ON THE FEMA
 WEBSITE. THERE WILL BE A ONE YEAR PHASE IN PERIOD
 DURING WHICH THE NEW FORM WILL BE VOLUNTARY.
  
 2ND REVIEW, PLEASE PROVIDE ELEVATION CERTIFICATE
 (CONSTRUCTION DRAWINGS) AS REQUESTED. INFORMATION SUCH
 AS PROPOSED ELEVATION, MECHANICAL EQUIPMENT ELEVATION,
 AND OTHER ITEMS WILL BE REVIEWED.
  
 2. LS 1.0, ARRANGEMENTS OF EXITS, SEE FBC 1015.2.1,
 EXIT DOORS TO BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED
 (ONE THIRD DISTANCE IF BUILDING IS SPRINKLERED, SEE
 EXCEPTION).
  
 PLEASE REVISE NOTE (WHICH STATES 1/3 DIAGONAL) AND
 DIMENSIONS AS REQUIRED.
  
 3. OK.
  
 4. LS 1.0, TRAVEL DISTANCE OF 114 FT 4 IN SHOWN FROM
 ONE CORNER TO OPPOSITE EXIT. PLEASE ALSO SHOW COMMON
 PATH AS IT APPEARS TO EXCEED 75 FEET, FBC 1014.3.
  
 2ND REVIEW, PLEASE REVISE TO SHOW COMMON PATH AS
 DEFINED BY FBC 1002:
  
 "THAT PORTION OF EXIT ACCESS WHICH THE OCCUPANTS ARE
 REQUIRED TO TRAVERSE BEFORE TWO SEPARATE AND DISTINCT
 PATHS OF EGRESS TRAVEL TO TWO EXITS ARE AVAILABLE" (NOT
 VISIBLE AS STATED ON PLAN). PLEASE CONTACT ME IF YOU
 WISH TO DISCUSS.
  
 5. OK
  
 6. NOTE THE FOLLOWING REGARDING PRODUCT APPROVALS
 FAC9N-3, FBC 1609:
  
 AC STAND - IF MANUFACTURED ONSITE, PROVIDE A DETAIL. IF
 MANUFACTURED OFF SITE, FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED
  
 ALUMINUM IMPACT BI PARTING CAR DOOR SYSTEM - PROVIDE
 PRODUCT APPROVAL TO VERIFY DESIGN PRESSURES, IMPACT,
 AND METHOD OF INSTALLATION. THIS MAY HAVE BEEN PROVIDED
 TO YOU WITH THE RECORDS RESEARCH REQUEST INFORMATION.
  
 PAIR 4X8 IMPACT STOREFRONT DOOR SYSTEM (DOOR A) - OK
  
 WINDOW WALL SYSTEM WITH DOOR (DOOR B) - OK
  
 IMPACT SINGLE DOOR (DOOR C) - OK
  
 ROOF - ULTRAGARD PVC SR 50 - THE ASSEMBLY SELECTED IS
 FOR WOOD DECK, PLAN SHOWS DOUBLE TEES. ENGINEERING
 REQUIRED FOR ZONES 2 AND 3 IF ASSEMBLY DESIGN PRESSURE
 DOES NOT MEET MINIMUMS SPECIFIED BY ENGINEER.
  
 NEW EIFS WALL SYSTEM - OK
  
 BUTT GLAZED WINDOW WALL SYSTEM (PRODUCT APPROVAL OR
 TEST REPORT AS PER A 5.0) - OK
  
 ANY INFORMATION NOT SUBMITTED PRIOR TO PERMIT ISSUANCE
 WILL BE REQUIRED TO BE SUBMITTED AS A REVISION. DESIGN
 PRESSURES TO MEET REQUIREMENTS ON S 7.1.
  
 7. OK.
  
 8. PLEASE PROVIDE THE ENERGY CALCS. THE DOCUMENT WHICH
 WAS UPLOADED WHICH IS NAMED LOADENERGYCALCULATIONS.PDF
 IS THE SAME DOCUMENT AS THE CIVIL COST ESTIMATE. SEE
 FBC 2010 ENERGY 103.2.3.
  
 9. OK.
  
 10. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE
 INFORMATION.
  
  
  