Plan Review Notes
Plan Review Notes For Permit 12090235
Permit Number 12090235
Review Stop B
Sequence Number 1
Notes
Date Text
2012-10-25 16:27:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD ZONE
 A8. WPB MUNICIPAL CODE 94 546(B), ALL NEW IMPROVEMENTS
 TO COMPLY WITH REQUIREMENTS FOR NEW CONSTRUCTION.
 FINISHED FLOOR SLAB TO BE AT A MINIMUM OF 16.5 FT. THE
 GRADING PLAN AND OTHER SHEETS SHOW A BUILDING ELEVATION
 OF 20.40 FT. PROPOSED CONSTRUCTION APPEARS TO COMPLY;
 PLEASE PROVIDE A SIGNED AND SEALED ELEVATION
 CERTIFICATE (CONSTRUCTION DRAWINGS). AN ADDITIONAL
 ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO C.O.
 (FINAL CONSTRUCTION). THE ELEVATION CERTIFICATE CAN BE
 EITHER THE FEMA 2009 ELEVATION CERTIFICATE FORM (OMB
 NO. 1660-0008, EXPIRES MARCH 31, 2012) OR ON THE NEW
 FORM WHICH WILL BE AVAILABLE NEXT WEEK ON THE FEMA
 WEBSITE. THERE WILL BE A ONE YEAR PHASE IN PERIOD
 DURING WHICH THE NEW FORM WILL BE VOLUNTARY.
  
 2. LS 1.0, ARRANGEMENTS OF EXITS, SEE FBC 1015.2.1,
 EXIT DOORS TO BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED
 (ONE THIRD DISTANCE IF BUILDING IS SPRINKLERED, SEE
 EXCEPTION). IT APPEARS THAT ITEMS 2 AND 4 WOULD BE
 RESOLVED BY INCLUDING THE ADDITIONAL DOUBLE DOOR AS AN
 EXIT, NOT CLEAR WHY THIS WAS EXCLUDED FROM LS PLAN AS
 AN EXIT.
  
 3. LS 1.0, THE HALLWAY TO THE BATHROOMS APPEARS TO BE A
 DEAD END, PLEASE PROVIDE DIMENSION ON THE LS PLAN.
  
 4. LS 1.0, TRAVEL DISTANCE OF 114 FT 4 IN SHOWN FROM
 ONE CORNER TO OPPOSITE EXIT. PLEASE ALSO SHOW COMMON
 PATH AS IT APPEARS TO EXCEED 75 FEET, FBC 1014.3.
  
 5. SECTION 2 A 4.0 AND OTHER DETAILS SHOW A WOOD TRUSS.
 PLEASE CLARIFY AND CONFIRM TYPE II B BUILDING TYPE OR
 REVISE ACCORDINGLY.
  
 6. NEED PRODUCT APPROVALS FOR:
  
 AC STAND
 ALUMINUM IMPACT BI PARTING CAR DOOR SYSTEM
 PAIR 4X8 IMPACT STOREFRONT DOOR SYSTEM (DOOR A)
 WINDOW WALL SYSTEM WITH DOOR (DOOR B)
 IMPACT SINGLE DOOR (DOOR C)
 ROOF - ULTRAGARD PVC SR 50
 NEW EIFS WALL SYSTEM
 BUTT GLAZED WINDOW WALL SYSTEM (PRODUCT APPROVAL OR
 TEST REPORT AS PER A 5.0)
  
 ANY INFORMATION NOT SUBMITTED PRIOR TO PERMIT ISSUANCE
 WILL BE REQUIRED TO BE SUBMITTED AS A REVISION. DESIGN
 PRESSURES TO MEET REQUIREMENTS ON S 7.1.
  
 7. INTERIOR WALL AND CEILING FINISH TO COMPLY WITH FBC
 803 (SEE ALSO 803.2). PROVIDE INFORMATION FOR THE WOOD
 GRAIN PLASTIC LAMINATE VENEER AS WELL AS METHOD OF
 ATTACHMENT, FBC 803.10.
  
 8. PLEASE PROVIDE THE ENERGY CALCS. THE DOCUMENT WHICH
 WAS UPLOADED WHICH IS NAMED LOADENERGYCALCULATIONS.PDF
 IS THE SAME DOCUMENT AS THE CIVIL COST ESTIMATE. SEE
 FBC 2010 ENERGY 103.2.3.
  
 9. OCCUPANCY CLASSIFICATION IS SHOWN AS BUSINESS;
 PLEASE INCLUDE THE PARTS AREA IN THE OCCUPANCY AS THIS
 BUILDING APPEARS TO BE MIXED USE. SEE FBC 508 REGARDING
 MIXED USE BUILDINGS, OCCUPANCY SEPARATIONS, AND
 NONSEPARATED OCCUPANCIES.
  
 10. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE
 INFORMATION.
  
  
  