2012-10-25 16:27:44 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD ZONE |
| A8. WPB MUNICIPAL CODE 94 546(B), ALL NEW IMPROVEMENTS |
| TO COMPLY WITH REQUIREMENTS FOR NEW CONSTRUCTION. |
| FINISHED FLOOR SLAB TO BE AT A MINIMUM OF 16.5 FT. THE |
| GRADING PLAN AND OTHER SHEETS SHOW A BUILDING ELEVATION |
| OF 20.40 FT. PROPOSED CONSTRUCTION APPEARS TO COMPLY; |
| PLEASE PROVIDE A SIGNED AND SEALED ELEVATION |
| CERTIFICATE (CONSTRUCTION DRAWINGS). AN ADDITIONAL |
| ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO C.O. |
| (FINAL CONSTRUCTION). THE ELEVATION CERTIFICATE CAN BE |
| EITHER THE FEMA 2009 ELEVATION CERTIFICATE FORM (OMB |
| NO. 1660-0008, EXPIRES MARCH 31, 2012) OR ON THE NEW |
| FORM WHICH WILL BE AVAILABLE NEXT WEEK ON THE FEMA |
| WEBSITE. THERE WILL BE A ONE YEAR PHASE IN PERIOD |
| DURING WHICH THE NEW FORM WILL BE VOLUNTARY. |
| |
| 2. LS 1.0, ARRANGEMENTS OF EXITS, SEE FBC 1015.2.1, |
| EXIT DOORS TO BE PLACED A DISTANCE APART EQUAL TO NOT |
| LESS THAN ONE HALF OF THE LENGTH OF THE MAXIMUM OVERALL |
| DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED |
| (ONE THIRD DISTANCE IF BUILDING IS SPRINKLERED, SEE |
| EXCEPTION). IT APPEARS THAT ITEMS 2 AND 4 WOULD BE |
| RESOLVED BY INCLUDING THE ADDITIONAL DOUBLE DOOR AS AN |
| EXIT, NOT CLEAR WHY THIS WAS EXCLUDED FROM LS PLAN AS |
| AN EXIT. |
| |
| 3. LS 1.0, THE HALLWAY TO THE BATHROOMS APPEARS TO BE A |
| DEAD END, PLEASE PROVIDE DIMENSION ON THE LS PLAN. |
| |
| 4. LS 1.0, TRAVEL DISTANCE OF 114 FT 4 IN SHOWN FROM |
| ONE CORNER TO OPPOSITE EXIT. PLEASE ALSO SHOW COMMON |
| PATH AS IT APPEARS TO EXCEED 75 FEET, FBC 1014.3. |
| |
| 5. SECTION 2 A 4.0 AND OTHER DETAILS SHOW A WOOD TRUSS. |
| PLEASE CLARIFY AND CONFIRM TYPE II B BUILDING TYPE OR |
| REVISE ACCORDINGLY. |
| |
| 6. NEED PRODUCT APPROVALS FOR: |
| |
| AC STAND |
| ALUMINUM IMPACT BI PARTING CAR DOOR SYSTEM |
| PAIR 4X8 IMPACT STOREFRONT DOOR SYSTEM (DOOR A) |
| WINDOW WALL SYSTEM WITH DOOR (DOOR B) |
| IMPACT SINGLE DOOR (DOOR C) |
| ROOF - ULTRAGARD PVC SR 50 |
| NEW EIFS WALL SYSTEM |
| BUTT GLAZED WINDOW WALL SYSTEM (PRODUCT APPROVAL OR |
| TEST REPORT AS PER A 5.0) |
| |
| ANY INFORMATION NOT SUBMITTED PRIOR TO PERMIT ISSUANCE |
| WILL BE REQUIRED TO BE SUBMITTED AS A REVISION. DESIGN |
| PRESSURES TO MEET REQUIREMENTS ON S 7.1. |
| |
| 7. INTERIOR WALL AND CEILING FINISH TO COMPLY WITH FBC |
| 803 (SEE ALSO 803.2). PROVIDE INFORMATION FOR THE WOOD |
| GRAIN PLASTIC LAMINATE VENEER AS WELL AS METHOD OF |
| ATTACHMENT, FBC 803.10. |
| |
| 8. PLEASE PROVIDE THE ENERGY CALCS. THE DOCUMENT WHICH |
| WAS UPLOADED WHICH IS NAMED LOADENERGYCALCULATIONS.PDF |
| IS THE SAME DOCUMENT AS THE CIVIL COST ESTIMATE. SEE |
| FBC 2010 ENERGY 103.2.3. |
| |
| 9. OCCUPANCY CLASSIFICATION IS SHOWN AS BUSINESS; |
| PLEASE INCLUDE THE PARTS AREA IN THE OCCUPANCY AS THIS |
| BUILDING APPEARS TO BE MIXED USE. SEE FBC 508 REGARDING |
| MIXED USE BUILDINGS, OCCUPANCY SEPARATIONS, AND |
| NONSEPARATED OCCUPANCIES. |
| |
| 10. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY |
| REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| |