Plan Review Notes
Plan Review Notes For Permit 12090229
Permit Number 12090229
Review Stop B
Sequence Number 1
Notes
Date Text
2012-09-12 17:16:55RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3.
 SEC. 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FLORIDA
 RESIDENTIAL CODE.
  
 3- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. IF THE GENERAL LIMITATION #7 FROM
 PRODUCT APPROVAL SUBMITTED REQUIRES RAS 117
 CALCULATIONS TO BE SIGNED AND SEALED, THEN THOSE
 CALCULATIONS NEED TO BE SIGNED AND SEALED. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE VALUATION AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL