Plan Review Notes For Permit 12090202 |
Permit Number |
12090202 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-09-17 10:02:16 | 12090202 | | 1801 PALM BEACH LAKES BLVD. | | TEMPORARY SITE LIGHTING. | | | | PROVIDE DETAIL ON THE SELECTED WIRING METHOD FOR THE | | LIGHTING. NEC 215.5, 225.4, 225.12, | | PROVIDE DETAIL AND ENGINEERING FOR THE LIGHT POLES WITH | | FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH | | WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE | | FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10 | | PROVIDE SIGNED AND SEALED WIND LOADING CERTIFICATION | | FOR THE LIGHT POLE ASSEMBLY WITH FIXTURES. 2010 FBC | | 1609.1., ASCE 7-10 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|