Plan Review Notes
Plan Review Notes For Permit 12090202
Permit Number 12090202
Review Stop E
Sequence Number 1
Notes
Date Text
2012-09-17 10:02:1612090202
 1801 PALM BEACH LAKES BLVD.
 TEMPORARY SITE LIGHTING.
  
 PROVIDE DETAIL ON THE SELECTED WIRING METHOD FOR THE
 LIGHTING. NEC 215.5, 225.4, 225.12,
 PROVIDE DETAIL AND ENGINEERING FOR THE LIGHT POLES WITH
 FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH
 WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE
 FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10
 PROVIDE SIGNED AND SEALED WIND LOADING CERTIFICATION
 FOR THE LIGHT POLE ASSEMBLY WITH FIXTURES. 2010 FBC
 1609.1., ASCE 7-10
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  