 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS IN THE TITLE BLOCK INFORMATION IS
 INCORRECTLY INDICATED AS "1000 OLD OKEESHOBEE DR."
  
 RESTAURANTS WITH AN OCCUPANT LOAD UNDER 50 PERSONS
 SHALL BE DEEMED A MERCANTILE OCCUPANCY.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 SEPERATE PLANS AND PERMITS NEEDED FOR TYPE 1 KITCHEN
 EXHAUST HOOD AND SUPPRESSION SYSTEM.
  