2012-09-18 10:23:29 | BUILDING PLAN REVIEW |
| PERMIT:12090196 |
| ADD: 1000-A OKEECHOBEE BLVD. |
| CONT: SOUTH PALM CONSTRUCTION |
| TEL: (561)301-81831 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| SEPT. 18 / 2012 |
| ACTION: DENIED |
| |
| NOTE: 2010 FBC-P ) 315.1 REQUIREMENTS. PUBLIC FOOD |
| SERVICE ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS |
| DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500 |
| FLORIDA STATUTES AND CHAPTER 509 FLORIDA STATUTES, |
| SHALL COMPLY WITH THE APPLICABLE CODE REQUIREMENTS |
| FOUND IN THE FLORIDA BUILDING CODE, BUILDING, CHAPTER |
| 4, SPECIAL DETAILED REQUIREMENTS BASED ON USE AND |
| OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO: |
| HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/ |
| PLANREVIEWINDEX.HTML |
| |
| 1) SHEET A4 VERSES A7: |
| |
| 1A) SHEET A4 THE FLOOR PLAN DEPICTS THE RESTROOM DOORS |
| BEING 21068 WHERE AS THE DOOR SCHEDULE INDICATES THE |
| DOORS AS 3068, PLEASE UPDATE THE DISCREPANCY, |
| WPB ADMINISTRATIVE CODE 107.2.1.3. |
| |
| 1B) SHEET A4 AT THE VESTIBULE OPENING IT APPEARS TO BE |
| A CASED OPENING WHERE AS A7 THE DOOR SCHEDULE IS |
| INDICATED AS DOOR 102, TYPE B DOOR PLEASE UPDATE THE |
| DISCREPANCY, WPB ADMINISTRATIVE CODE 107.2.1.3. |
| |
| 1C) SHEET A4 THE DOUBLE ACTION DOOR THAT LEADS INTO THE |
| KITCHEN IS DEPICTED AS 30 INCH DOOR WITH A WALL SECTION |
| ADJACENT BEING 18 INCHES WHEN A DOOR MEETING THE |
| ACCESSIBLITY CODE IS PROVIDED THEN THE ADJACENT WALL |
| WILL NOT MEET THE REQUIREMENTS OF 2010 ACESSIBILITY |
| CODE 404.2.4 MANEUVERING CLEARENCES. |
| |
| 2) SHEET A4 VESTIBULE WIDTH OF 3'-8 1/2" PLEASE REVIEW |
| 2010 ACCESSIBILITY FIGURE 404.2.4.1(H) WHICH REQUIRES |
| THE VESTIBULE TO BE A MINIMUM OF 48 INCHES IN WIDTH. |
| |
| 3) SHEET A3 VS P1, THE A3 SHEET LIFE SAFETY SHEET DOE |
| NOT INDICATE WHICH WALL IS A TENANT SEPERATION WALL AS |
| IS INDICATED ON THE P1 SHEET. PLEASE PROVIDE |
| WALL RATING AT THE TENANT SEPERATION WALL. 2010 FBC-B |
| 709.1.6. WALLS SEPERATING INDIVIDUAL TENANT SPACES. |
| |
| 4) SHEET A1, OCCUPANCY TYPE IS LISTED AS A A2 RESTARANT |
| PLEASE REVIEW 2010 FBC-B SECTION 303.1.1. RESTAURANTS |
| AND DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF |
| LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS GROUP M, |
| MERCANTILE. |
| |
| 5) SHEET A1 OCCUPANCY SEPERATION IS INDICATED AS A2 TO |
| A2 ONLY TENANT SEPERATION REQUIRED, WITH THE NEW |
| RESTARAUNT BEING CLASSIFIED AS MERCANTILE AND THE |
| ADJACENT TENANT BEING A A2 RESTARAUNT THEN 2010 FBC-B |
| TABLE 508.3.3 NON-SPRINKLERED WILL REQUIRE A 2 HOUR |
| FIRE RATED WALL. |
| |
| 6) PLUMBING SHEET P2 INDICATES THE GREAT BASIN GREASE |
| SEPERATOR TO BE LOCATED ON THE EXTERIOR OF THE |
| BUILDING, PLEASE BE AWARE THAT TRAFFIC PATERNS DO |
| SURROUND THIS BUILDING AND A DETAIL FOR CONCRETE PAD |
| WILL BE REQUIRED AND TRAFFIC BEARING TOP FOR GREASE |
| INTERCEPTOR, PLEASE SEE MANUFACTURERS SPECIFICATIONS |
| GREAT BASIN INSTALATION, OPERATION AND MAINTENANCE |
| GUIDE SHEET 3 OF 7 REV. 3 11/07/11. |
| |
| 7) SHEET A4 INDICATES A NEW EXTERIOR FRONT DOOR, THE |
| DESIGNER OF RECORD INDICATES TYPE OF UNIT TO BE |
| INSTALLED BUT THE CONTRACTOR DID NOT PROVIDE PRODUCT |
| APPROVAL FOR THIS DOOR. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 8) SHEET A7 ROOM FINISH SCHEDULE INDICATES THE USE OF |
| MR BOARD IN THE RESTROOMS BUT THE PLANS ARE SILENT TO |
| THE FINISH AROUND THE WET AREAS THERE IS TWO INFORMAL |
| INTERPRETATIONS FROM BOAF ON SECTION 1210.2 THAT THE |
| CODE SECTION DOES NOT REGULATE THE TYPE OF WALL |
| MATERIAL, JUST THE FINISH ON THE WALL. THE FINAL |
| DECISION MUST BE MADE BY THE LOCAL JURISDICTION AS TO |
| WHAT IS CONSIDERED HARD, SMOOTH AND NON-ABSORBENT. THE |
| BUILDING OFFICIAL HAS ALLOWED THE USE OF EPOXY PAINT ON |
| MR BOARD AS A HARD, SMOOTH AND NON-ABSORBENT SURFACE. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |