2012-09-12 11:56:52RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SELECTED FLAT ROOF ASSEMBLY W-32 FROM PRODUCT
 APPROVAL FL 1654 DOESN'T MEET THE DESIGN PRESSURES FOR
 CORNER AREAS AS REQUIRED BY SEC. R301.2.1.4.3 OF 2010
 FLORIDA RESIDENTIAL CODE. NEED TO SELECT ANOTHER
 ASSEMBLY THAT MEETS SUCH DESIGN PRESSURES.
  
 2- SPECIFY HOW IS THE CONCRETE TILE GOING TO BE
 INSTALLED. IF USING ADHESIVE THEN, PROVIDE PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9N-3. SEC. 107.2.1.2
 CITY AMENDMENTS TO FBC.
  