2012-09-20 12:15:0112090168
 359 PALMETTO
 SFD RENOVATION
  
 THE SCOPE OF THE ELECTRICAL CHANGES PROPOSED IS NOT
 CLEAR. PLEASE PROVIDE THE FOLLOWING:
  
 PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH PANELS,
 MAIN BREAKERS, WIRE SIZES, GROUNDING ETC. INDICATE THE
 LOCATION OF THE SERVICE, DEPTH OF CONDUCTORS ETC.
 VERIFY THE UNDER GROUND ELECTRICAL SERVICE IS LOCATED
 MORE THAN 5 FEET FROM THE SWIMMING POOL. SHOW LOCATION
 OF ALL PANEL BOARDS. NEC 215.15, 680.10
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ALL EXTERIOR RECEPTACLES REQUIRE GROUND FAULT
 PROTECTION. NEC 210.8
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER