2013-01-14 11:03:14 | BUILDING REVIEW THIRD CHECKLIST. | | CODE: 2010 FBC. | | | | 1- ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED | | FOR THE FLAT ROOF ASSEMBLY. ACCORDING TO THE CALCULATED | | DESIGN PRESSURES SUBMITTED AND THE SELECTED APPROVED | | ASSEMBLY TO BE USED, THE NAIL ENHANCING SHALL BE 6"O.C. | | FOR THE PERIMETER AREA AND 4"O.C. FOR THE CORNER AREA. | | REVISE CALCULATIONS AS REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|