2012-12-27 09:25:01RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- STORAGE WALL SECTION B/A-1: VENTS SPECIFIED DON'T
 PROVIDE CROSS VENTILATION AS REQUIRED BY SEC. R806.
 CALCULATIONS SUBMITTED DON'T WORK BECAUSE THIS IS A
 FLAT ROOF AND THERE IS NOT CROSS VENTILATION WHEN VENTS
 ARE SPREAD. REVISE AS REQUIRED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. (REPEAT COMMENT. NOT SUBMITTED).
  
 B) STORM PANELS SHUTTER. NOA 07-0817.03 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA AND RESUBMIT. (REPEAT COMMENT.
 NOT SUBMITTED).
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF HURRICANE STORM PANELS. SHOW SPECIFIC
 PANELS MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED.
 ***NOTE: TAKE INTO CONSIDERATION THE GLASS SEPARATION
 REQUIRED. SEE SHUTTERS NOA. SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED. ALSO, NEED
 TO COORDINATE WITH ITEM #2(B) ABOVE).
  
 ***NOTE: CLARIFY IF USING IMPACT WINDOWS OR NON-IMPACT
 WINDOWS. NOA 06-0608.03 SUBMITTED NOW IS FOR IMPACT
 WINDOWS. THEREFORE, IMPACT WINDOWS DON'T REQUIRE STORM
 SHUTTERS.
  
 5- FLAT ROOF PRODUCT APPROVAL SUBMITTED. SPECIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA 07-1219.09
 SUBMITTED. NEED THE NAIL ENHANCING TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 ***NOTE; NEW ENGINER OF RECORD RESPONDED: "THE NOA
 NOTES THAT THE WIND PRESSURES ARE ACCEPTABLE. THE ROOF
 AREAS ARE BOTH UNDER 400 SQUARE FEET IN AREA".
 A) ENGINEER TO CLARIFY WHERE IN THE FLORIDA BUILDING
 CODE OR ASCE STANDARD STATES THAT ROOF AREAS UNDER 400
 S.F. ARE EXEMPT FROM DESIGN PRESSURES. ROOF ASSEMBLIES
 ARE COMPONENTS AND CLADDING WHERE PERIMETER AND CORNER
 AREAS HAVE GREATER DESIGN PRESSURES. THAT'S WHY GENERAL
 LIMITATION #7 ALLOWS NAIL ENHANCING CALCULATIONS. ON
 THE OTHER HAND, GENERAL LIMITATION #9 DOESN'T ALLOW
 NAIL ENHANCING AND CAN'T BE USED.
  
 B) ENGINEER TO REVIEW RAS 117 AND SPECIFIC APPROVED
 ASSEMBLY FROM NOA PROVIDED. AND, THEN PROVIDE THE
 REQUIRED CALCULATIONS. THESE CALCULATIONS ARE TO
 DETERMINE THE PROPER ATTACHMENT OF ANCHOR AND/OR BASE
 SHEETS AND INSULATION PANELS ON FLAT ROOF. THESE
 CALCULATIONS ARE FOR CLADDING FASTENERS AND THE
 EFFECTIVE WIND AREA SHALL NOT BE GREATER THAN THE AREA
 THAT IS TRIBUTARY TO AN INDIVIDUAL FASTENER. SEE ALSO
 COMPONENT AND CLADDING TABLE R301.2(2) OF 2010
 FBC-RESIDENTIAL
  