Plan Review Notes
Plan Review Notes For Permit 12090154
Permit Number 12090154
Review Stop B
Sequence Number 1
Notes
Date Text
2012-10-04 14:09:01RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL..
  
 1- PORCH SECTION A/A-1:
 A) SIMPSON THA218 HANGER SPECIFIED BY THE ENGINEER CAN
 NOT BE USED UPSIDE DOWN AND IT IS NOT DESIGNED FOR
 UPLIFT. SEE SIMPSON CATALOG AND REVISE CONNECTOR AS
 REQUIRED. OR, PROVIDE COMPLETE ENGINEERING ANALYSIS
 SHOWING HOW THIS CONNECTOR IS SUITABLE FOR THE PROPOSED
 INSTALLATION. SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC.
  
 B) SPECIFY SLOPE OF ROOF. SEC. R905.11.1 OF 2010
 FBC-RESIDENTIAL.
  
 C) SPECIFY ROOF SHEATHING NAIL SIZE AND SPACING. NEED
 8D RING SHANK NAILS MIN. AND ZONE 3 REQUIRES NAILS AT
 4"O.C.. SEC. R803..2.3.1.
  
 D) 2X10 ROOF RAFTERS ARE SPACED AT 24" O.C. OR 16" O.C.
 BOTH SPECIFICATIONS ARE SHOWN ON THE SAME WALL SECTION.
 REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 E) SPECIFY ROOF CROSS VENTILATION. SEC. R806.
  
 F) SPECIFY FOOTING SIZE AND REINFORCEMENT. SEC. 107.2.1
 CITY AMENDMENTS.
  
 2- STORAGE WALL SECTION B-A-1:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR NEW CONCRETE
 SLAB. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) SPECIFY FOOTING SIZE AND REINFORCEMENT. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) PROVIDE ALL THE RELEVANT INFORMATION THAT WAS
 REQUESTED ON ITEM #1 ABOVE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- WIND INFORMATION:
 A) PROVIDE ALL THE DESIGN LOADS AS REQUIRED BY SEC.
 R301.1.
  
 B) SPECIFY THE INTERNAL PRESSURES COEFFICIENT. "CH 16
 FBC" DOESN'T PROVIDE ANY-SPECIFIC DESIGN INFORMATION.
 ENGINEER NEEDS TO PROVIDE SPECIFIC DESIGN INFORMATION
 NOT CITING THE CODE. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- SCOPE OF WORK NOTES: WHERE ARE THE OUTSIDE BAR AND
 APPLIANCES SPECIFIED ON NOTE #3?. ALSO, PORCH AREA IS
 NOT CONSIDERED A LIVABLE AREA. REVISE AS REQUIRED.
 PROVIDE CLEAR INFORMATION AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 5- PROVIDE COMPLETE FRAMING DETAILS FOR NEW EXTERIOR
 DOOR. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
  
 B) FIBERGLASS EXTERIOR DOOR. PROVIDE PRODUCT APPROVAL
 FOR DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED BY
 THE ENGINEER. AND, NOA 06-1212.01 EXPIRED ON 9-6-12.
  
 C) STORM PANELS SHUTTER. NOA 07-0817.03 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA AND RESUBMIT.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 ALSO, PRODUCT APPROVALS SUBMITTED HAVE AN ENGINEER'S
 REVIEW STAMP, BUT THE ENGINEER DIDN'T SIGN THE STAMP.
 MAKE SURE ALL THE PRODUCT APPROVALS REVIEW STAMP ARE
 SIGNED BY THE ENGINEER.
  
 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF HURRICANE STORM PANELS. SHOW SPECIFIC
 PANELS MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED.
 ***NOTE: TAKE INTO CONSIDERATION THE GLASS SEPARATION
 REQUIRED. SEE SHUTTERS NOA. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- FLAT ROOF PRODUCT APPROVAL SUBMITTED. SPECIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1.4.3, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712