Plan Review Notes
Plan Review Notes For Permit 12090136
Permit Number 12090136
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-01-12 11:35:45444 WEST RAILROAD AVENUE - SUITE #400
 PERMIT #12090136
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS1.1 - NEW COMMENT IN RESPONSE TO THE
 ARCHITECTURAL RESPONSE LETTER: THE MAXIMUM DEAD-END
 CORRIDOR PERMITTED IN STORAGE OCCUPANCIES IS 20 FEET
 PER TABLE 42.2.5 (FFPC - NFPA 101 W/ FLORIDA
 AMENDMENTS).
 (ORIGINAL COMMENT : A DEAD-END CORRIDOR OF 85 FEET IS
 CREATED WHEN MEASURED FROM THE DOOR OF TELEPHONE #415
 TO THE END OF HALLWAY #412.)
  
 SHEET LS1.1: NEW COMMENT IN RESPONSE TO THE
 ARCHITECTURAL RESPONSE LETTER: ALL STAIR DOORS MUST
 UNLOCK TO ALLOW RE-ENTRY IF USING THE BUILDING FIRE
 ALARM SYSTEM IN LIEU OF DOORS ALWAYS ALLOWING FREE
 INGRESS/EGRESS.
 (ORIGINAL COMMENT: STAIR DOOR A-1 APPEARS TO BE LOCKED
 FROM THE STAIR SIDE, WHICH IS ACCEPTABLE AS LONG AS
 STAIR RE-ENTRY IS PROVIDED FOR ALL STAIR DOORS ON THE
 5TH FLOOR. STAIR SIGNAGE INDICATING WHICH FLOORS HAVE
 STAIRWELL RE-ENTRY TO BE PROVIDED.)
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]