2012-11-01 16:46:00 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2010 |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PAGE M2.1.1: AT STAIR A-1 ENTRANCE, FLOOR PLAN SHOWS |
| TWO FIRE DAMPERS IN LOCATIONS WHERE WALLS NO LONGER |
| EXIST. THE DESIGN INTENT IS UNCLEAR. PLEASE CLARIFY AND |
| SHOW FIRE DAMPERS IN THEIR PROPER LOCATION PER FBC-M |
| 607.8 AND FBC-B 106.1. |
| |
| 2. PAGE M2.1.1: KEY NOTES 1 AND 2 CALL FOR DUCT |
| PENETRATIONS OF THE FLOOR/CEILING ASSEMBLY BETWEEN THE |
| 4TH AND 5TH FLOORS. SHOW HOW THESE PENETRATIONS OF THIS |
| RATED ASSEMBLY ARE TO BE PROTECTED PER FBC-M 607.5. |
| |
| 3. PAGE M2.1.1: SEVERAL AREAS INVOLVING EVIDENCE |
| STORAGE ARE SHOWN ON LIFE SAFETY PLAN TO HAVE FIRE |
| RESTSTANCE RATED WALLS. NONE OF THE DUCT PENETRATIONS |
| OR TRANSFER OPENINGS IN THESE AREAS ARE SHOWN TO BE |
| PROTECTED. SHOW HOW THESE PENETRATIONS AND TRANSFER |
| OPENINGS ARE TO BE PROTECTED PER FBC-M 607.5. |
| |
| 4. PAGE M2.1.2: WEAPONS CLEANING ROOM 423 SHOWS AN |
| EXHAUST FAN ABOVE THE CEILING IN THE PLENUM SPACE. |
| EXHAUST DUCT UNDER POSITIVE PRESSURE (DISCHARGE SIDE OF |
| FAN) SHALL NOT BE LOCATED IN A RETURN AIR PLENUM PER |
| FBC-M 601.5. SHOW HOW THIS DUCT IS TO BE ISOLATED FROM |
| THE PLENUM SPACE (RETURN AIR COULD BE ELIMINATED FROM |
| THIS ROOM, WITH CEILING SPACE ISOLATED FROM THE |
| PLENUM). |
| |
| 5. PAGE M0.1: OUTSIDE AIR CALCULATIONS SHOW TRAINING |
| AREA WITH AN OCCUPANT LOAD OF 24 PERSONS WHILE THE |
| FLOOR PLAN SHOWS AT LEAST 67 SEATS IN THIS SPACE. |
| PROVIDE A CALCULATION SHOWING THE ACTUAL OCCUPANT LOAD |
| OF THIS SPACE PER FBC-M SECTION 403. |
| |