Plan Review Notes
Plan Review Notes For Permit 12090136
Permit Number 12090136
Review Stop M
Sequence Number 1
Notes
Date Text
2012-11-01 16:46:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M2.1.1: AT STAIR A-1 ENTRANCE, FLOOR PLAN SHOWS
 TWO FIRE DAMPERS IN LOCATIONS WHERE WALLS NO LONGER
 EXIST. THE DESIGN INTENT IS UNCLEAR. PLEASE CLARIFY AND
 SHOW FIRE DAMPERS IN THEIR PROPER LOCATION PER FBC-M
 607.8 AND FBC-B 106.1.
  
 2. PAGE M2.1.1: KEY NOTES 1 AND 2 CALL FOR DUCT
 PENETRATIONS OF THE FLOOR/CEILING ASSEMBLY BETWEEN THE
 4TH AND 5TH FLOORS. SHOW HOW THESE PENETRATIONS OF THIS
 RATED ASSEMBLY ARE TO BE PROTECTED PER FBC-M 607.5.
  
 3. PAGE M2.1.1: SEVERAL AREAS INVOLVING EVIDENCE
 STORAGE ARE SHOWN ON LIFE SAFETY PLAN TO HAVE FIRE
 RESTSTANCE RATED WALLS. NONE OF THE DUCT PENETRATIONS
 OR TRANSFER OPENINGS IN THESE AREAS ARE SHOWN TO BE
 PROTECTED. SHOW HOW THESE PENETRATIONS AND TRANSFER
 OPENINGS ARE TO BE PROTECTED PER FBC-M 607.5.
  
 4. PAGE M2.1.2: WEAPONS CLEANING ROOM 423 SHOWS AN
 EXHAUST FAN ABOVE THE CEILING IN THE PLENUM SPACE.
 EXHAUST DUCT UNDER POSITIVE PRESSURE (DISCHARGE SIDE OF
 FAN) SHALL NOT BE LOCATED IN A RETURN AIR PLENUM PER
 FBC-M 601.5. SHOW HOW THIS DUCT IS TO BE ISOLATED FROM
 THE PLENUM SPACE (RETURN AIR COULD BE ELIMINATED FROM
 THIS ROOM, WITH CEILING SPACE ISOLATED FROM THE
 PLENUM).
  
 5. PAGE M0.1: OUTSIDE AIR CALCULATIONS SHOW TRAINING
 AREA WITH AN OCCUPANT LOAD OF 24 PERSONS WHILE THE
 FLOOR PLAN SHOWS AT LEAST 67 SEATS IN THIS SPACE.
 PROVIDE A CALCULATION SHOWING THE ACTUAL OCCUPANT LOAD
 OF THIS SPACE PER FBC-M SECTION 403.
  