2012-10-05 10:17:57 | 444 WEST RAILROAD AVENUE - SUITE #400 |
| PERMIT #12090136 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL: ALL DEMOLITION AND CONSTRUCTION AREAS SHALL |
| HAVE "NO SMOKING" SIGNS POSTED. |
| |
| GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY |
| THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| DIXIE HIGHWAY. |
| |
| GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A |
| MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A |
| LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO |
| EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| GENERAL: INDICATE THE MAXIMUM INCARCERATION TIME FOR |
| INDIVIDUALS LOCATED IN THE HOLDING CELLS. |
| |
| SHEET LS1.1: A DEAD-END CORRIDOR OF 85 FEET IS CREATED |
| WHEN MEASURED FROM THE DOOR OF TELEPHONE #415 TO THE |
| END OF HALLWAY #412. |
| |
| SHEET LS1.1: A COMMON PATH OF TRAVEL OF 112 FEET IS |
| CREATED WHEN MEASURED FROM MEN'S LOCKER #407 TO STAIR |
| #A-2. |
| |
| SHEET LS1.1: WHERE EXIT ACCESS FROM ONE OCCUPANCY TYPE |
| TRAVERSES ANOTHER OCCUPANCY TYPE, THE MULTIPLE |
| OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY (NFPA |
| 101 - 6.1.14.1.2). THIS FLOOR IS FUNCTIONING AS A |
| NON-SEPARATED MIXED USE (BUSINESS, STORAGE AND |
| ASSEMBLY) OCCUPANCY. PROVIDE AN OCCUPANT LOAD BREAKDOWN |
| FOR EACH ROOM. THE MOST STRINGENT LIFE SAFETY |
| REQUIREMENTS FOR EACH OCCUPANCY TYPE WILL APPLY. FOR |
| EXAMPLE, ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD |
| EXCEEDING 100 PERSONS SHALL HAVE PANIC OR FIRE EXIT |
| HARDWARE ON EXIT AND EXIT ACCESS DOORS. |
| |
| SHEET LS1.1: STAIR DOOR A-1 APPEARS TO BE LOCKED FROM |
| THE STAIR SIDE, WHICH IS ACCEPTABLE AS LONG AS STAIR |
| RE-ENTRY IS PROVIDED FOR ALL STAIR DOORS ON THE 5TH |
| FLOOR. STAIR SIGNAGE INDICATING WHICH FLOORS HAVE |
| STAIRWELL RE-ENTRY TO BE PROVIDED. |
| |
| SHEET LS1.1: TRAINING ROOM #405 - DOORS SHALL SWING IN |
| THE DIRECTION OF TRAVEL WHEN SERVING AN OCCUPANT LOAD |
| OF 50 OR MORE PERSONS. |
| |
| SHEET E3.1.1: CARD READERS ARE NOT PERMITTED IN THE |
| EXIT STAIR ENCLOSURE PER NFPA 101 SECTION 7.1.3.2.1(9). |
| |
| SHEET FA2.1.1: NO AUDIBLE FIRE ALARM NOTIFICATION |
| APPLIANCES LOCATED TO THE EAST OF THE MAIN CORRIDOR. IT |
| MAY BE DIFFICULT TO MEET THE MINIMUM AUDIBILITY |
| REQUIREMENTS OF NFPA 72 WITH SO FEW APPLIANCES. |
| |
| SHEET FA2.1.2: PROVIDE SMOKE DETECTOR IN PROCESSING |
| ROOM TO ALLOW EARLY FIRE DETECTION IN AREA OF HOLDING |
| CELLS. PROVIDE A STROBE DEVICE IN THE SUPPLIES ROOM. |
| |
| FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING |
| PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| AUTOMATIC FIRE SPRINKLERS. NO SPRINKLER PLANS |
| SUBMITTED. PER FLORIDA ADMINISTRATIVE CODE SECTION |
| 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| SUCH AS PRE-ENGINEERED SYSTEMS. |
| |