2012-09-26 16:57:33 | BUILDING PLAN REVIEW |
| PERMIT: 12090136 |
| ADD: 444 W RAILROAD AVE #400 |
| CONT: TBD |
| TEL: (561)###-#### |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| SEPT. 26/ 2012 |
| ACTION: DENIED |
| |
| 1) SHEET LS1.1 GENERAL BUILDING DATA, BUILDING TYPE IS |
| INDICATED AS A IIIB PLEASE RECLASSIFY THE BUILDING. |
| THIS BUILDING WAS BUILT UNDER THE 2001 FBC-B AND WAS |
| CLASSIFIED AS MINIMUM BUILDING TYPE II, UNDER THE 2010 |
| CODE THE BUILDING IS CLASSIFIED AS A IB SEE CODE |
| CONVERSIONS 2001 TO 2004 FBC. |
| |
| 2) SHEET LS1.1 LIFE SAFETY SHEET IS MISSING CERTAIN |
| CODE CRITERIA: |
| 2010 FBC-B 107.3.5.1.1(6) OCCUPANCY LOAD/ EGRESS |
| CAPACITY AT DOORS AND STAIRS, TABLE 1004.1.1. |
| |
| 3) SHEET A1.1 INDICATES A WALL TYPE TAG AS A WT-5 FOR |
| ALL TENANT SEPERATION WALLS THAT ARE COMMON TO ELEVATOR |
| LOBBY 410 AND CORRIDORS COMMON CORRIDORS426 & 427. |
| SHEET A4.2 WALL TYPES ONLY INDICATE WALL TAG TYPE WT-6 |
| AS A 1 HOUR FIRE RATED WALL. 2010 FBC-B 709.1(6) |
| REQUIRES A 1 HOUR FIRE RATING. MECHANICAL SHEETS |
| INDICATE FIRE RATED DAMPERS IN THESE WALLS AS WALL. |
| |
| 4) SHEET A4.1 DOOR SCHEDULE DOES NOT INDICATE THESE |
| DOORS BEING RATED DOORS, ALL DOORS (TENANT DOORS) |
| WITHIN COMMON CORRIDOR WALLS (TENANT SEPERATION WALLS) |
| SHOULD BE FIRE RATED PER 2010 FBC-B TABLE 715.4. RATED |
| DOORS 19, 20, 32, 40 , 47.AND OR 49. 49 MAY OR MAY NOT |
| REQUIRE FIRE RATING IS THE DEA ELEVATOR LOBBY LOCKED |
| OFF TO THE PUBLIC AND CONSIDERED TENANT SPACE? |
| |
| 5) SHEET A1.1 PLEASE REVIEW COMMON PATH OF TRAVEL FROM |
| THE FURHTEST POINT IN WEAPONS STORAGE ROOM # 424 TO |
| DOOR # 32 APPROXIMATELY 112 FEET WHICH EXCEEDS THE 100 |
| FOOT LIMIT UNDER 1014.3 BUSINESS OCCUPANCY FULLY |
| SPRINKLERED. |
| |
| 6) SHEET A1.1 HOLDING CELLS 1-3 PLEASE PROVIDE |
| COMPLIANCE WITH 2010 ACCESSIBILITY CODE 807 (1-3) |
| HOLDING CELLS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |