2012-09-28 10:24:22 | BUILDING PLAN REVIEW |
| PERMIT: 12090092 |
| ADD: 1901 N FLAGLER DR |
| CONT: IBIS BUILDING CORP |
| TEL: (561)307-4951 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| SEPT. 28/ 2012 |
| ACTION: DENIED |
| |
| 1) SHEET A-1 NOTE # 14 INDICATES THE USE OF FIRE |
| DAMPERS FOR THE DUCTS PENETRATING THE 2ND FLOOR. |
| NEITHER THE A OR M SHEETS SHOW DEVICES IN THE DRAWINGS |
| NOR IS THE FIRE RATING IN HOURS PROVIDED OR DETAIL FOR |
| FIRE DAMPER PENETRATING THE 2ND FLOOR/ CEILING |
| ASSEMBLY: |
| |
| 2010 FBC-B 713.1.1 DUCTS AND AIR TRANSFER OPENINGS. |
| |
| PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS |
| THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH |
| SECTIONS 713.2 THROUGH 713.3.3. PENETRATIONS OF |
| HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS |
| PERMITTED BY EXCEPTION 4 OF SECTION 708.2, AND NOT |
| REQUIRED TO BE PROTECTED WITH FIRE DAMPERS BY OTHER |
| SECTIONS OF THIS CODE, SHALL COMPLY WITH SECTIONS 713.4 |
| THROUGH 713.4.2.2. DUCTS AND AIR TRANSFER OPENINGS THAT |
| ARE PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTION |
| 716. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |