Plan Review Notes For Permit 12090086 |
Permit Number |
12090086 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-09-07 14:39:58 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ARCHITECT TO REVISE PROPOSED BASE SHEET ENHANCED | | FASTENING SCHEDULE. ACCORDING TO RAS 117 SEC. 8.1 THE | | MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4" | | O.C.. CALCULATIONS SUBMITTED SHOW 3.8" FASTENER SPACING | | FOR ROOF ZONE #3. ARCHITECT ROUNDED UP THE FASTENER | | SPACING TO 4" O.C. AFTER CALCULATIONS ARE DONE, THEN | | THE NUMBER SHALL BE ROUNDED DOWN NOT ROUNDED UP. SEE | | RAS 117 SEC. 10.4.5 AND REVISE AS REQUIRED. | | | | 2- ARCHITECT TO REVISE THE MINIMUM EDGE DISTANCE. | | ACCORDING TO FIGURE R301.2(7) OF 2010 FLORIDA | | RESIDENTIAL CODE THE MINIMUM DIMENSION FOR "A" IS 4 | | FEET IN ALL CASES. SEE FOOT NOTE ON FIGURE R301.2(7) | | AND REVISE DIMENSION FOR ROOF AREA 2 AND ROOF AREA 3 AS | | REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, 0PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|