2012-09-07 14:39:58RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ARCHITECT TO REVISE PROPOSED BASE SHEET ENHANCED
 FASTENING SCHEDULE. ACCORDING TO RAS 117 SEC. 8.1 THE
 MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4"
 O.C.. CALCULATIONS SUBMITTED SHOW 3.8" FASTENER SPACING
 FOR ROOF ZONE #3. ARCHITECT ROUNDED UP THE FASTENER
 SPACING TO 4" O.C. AFTER CALCULATIONS ARE DONE, THEN
 THE NUMBER SHALL BE ROUNDED DOWN NOT ROUNDED UP. SEE
 RAS 117 SEC. 10.4.5 AND REVISE AS REQUIRED.
  
 2- ARCHITECT TO REVISE THE MINIMUM EDGE DISTANCE.
 ACCORDING TO FIGURE R301.2(7) OF 2010 FLORIDA
 RESIDENTIAL CODE THE MINIMUM DIMENSION FOR "A" IS 4
 FEET IN ALL CASES. SEE FOOT NOTE ON FIGURE R301.2(7)
 AND REVISE DIMENSION FOR ROOF AREA 2 AND ROOF AREA 3 AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, 0PLEASE CALL