| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THE PERMIT APPLICATION INDICATES BOTH AN ADDRESS AND A |
| SUITE NUMBER OF 412. IS THIS ACCURATE? |
| |
| THE PERMIT APPLICATION DOES NOT INDICATE THIS IS A |
| CHANGE OF USE FROM A BUSINESS OCCUPANCY TO AN ASSEMBLY |
| OCCUPANCY. |
| |
| UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL |
| DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. |
| |
| EVERY ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD |
| OF THE ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN |
| EXIT FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE |
| THE NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| INDICATE THE LOCKING/LATCHING MECHANISM FOR THE |
| EXISTING EXIT DOORS. |
| |
| SHEET A-1: PROVIDE AN EXIT SIGN IN THE DINING AREA |
| INDICATING THERE IS A SECONDARY EXIT IN THE REAR OF THE |
| BUILDING. |
| |
| SHEET M-1: VERIFY THERE ARE EXISTING DUCT SMOKE |
| DETECTOR(S) FOR THE 10-TON UNIT. |
| |