2012-09-08 14:40:24412 CLEMATIS STREET - SUITE #412
 PERMIT #12090015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES BOTH AN ADDRESS AND A
 SUITE NUMBER OF 412. IS THIS ACCURATE?
  
 THE PERMIT APPLICATION DOES NOT INDICATE THIS IS A
 CHANGE OF USE FROM A BUSINESS OCCUPANCY TO AN ASSEMBLY
 OCCUPANCY.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 EVERY ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD
 OF THE ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN
 EXIT FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE
 THE NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INDICATE THE LOCKING/LATCHING MECHANISM FOR THE
 EXISTING EXIT DOORS.
  
 SHEET A-1: PROVIDE AN EXIT SIGN IN THE DINING AREA
 INDICATING THERE IS A SECONDARY EXIT IN THE REAR OF THE
 BUILDING.
  
 SHEET M-1: VERIFY THERE ARE EXISTING DUCT SMOKE
 DETECTOR(S) FOR THE 10-TON UNIT.
  