Date |
Text |
2012-09-05 16:53:54 | 12090015 | | 412 CLEMATIS STREET #412 | | FIELD OF GREENS | | | | PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS | | WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT ALL | | TIMES. INCLUDE A RISER PLAN SHOWING THE EXISTING | | ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECTS. NEC | | 110.26, 215.5, 240.24 | | | | PROVIDE A DETAIL VERIFYING THE REQUIRED WORKING | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | PROVIDED FOR THE ELECTRICAL PANEL BOARDS. NEC 110.26, | | 240.24, 408.17 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|