2012-09-12 07:07:54BUILDING PLAN REVIEW
 PERMIT: 12090015
 ADD: 412 CLEMATIS ST.
 CONT: ANDERSON-MOORE CORP
 TEL: (561)662-1819
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 12/ 2012
 ACTION: DENIED
  
 1) SHEET A1 GENERAL BUILDING CODE ANALYSIS INDICATES
 THIS TO BE A CHANGE OF OCCUPANCY, PLEASE UPDATE THE
 PERMIT APPLICATION TO INDICATE A CHANGE OF OCCUPANCY,
 2010 EXISTING BLDG CODE :
 901.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 901.4 CERTIFICATE OF OCCUPANCY REQUIRED.
 A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED WHERE A
 CHANGE OF OCCUPANCY OCCURS THAT RESULTS IN A DIFFERENT
 OCCUPANCY CLASSIFICATION AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) SHEET A1 THE CURRENT CONFIGURATION OF THE EXISTING
 RESTROOMS DOES NOT MEET THE REQUIREMENTS OF THE 2010
 FLORIDA ACCESSIBILITY CODE WITH THE REQUIRED 60 INCHES
 WHERE NO OTHER FIXTURES (LAVATORY) OR OBSTRUCTIONS
 SHALL BE LOCATED WITHIN THE WATER CLOSET CLERANCES. SEE
 FIGURE 604.8.1.6.
 PLEASE REVIEW SECTION S 2010 FL ACCESSIBLITY SECTIONS
 202.4.1 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 AN ADDITIONAL $19,000.00 WILL NEED TO BE SPENT IN
 UPGRADING TO MEET THE 2010 ACCESSIBILITY CODE.
  
 3) PLEASE UPDATE CODE SECTIONS LISTED UNDER THE HEADING
 LIFE SAFETY LEGEND WITH 2007 FBC REFERENCES. SEE 2010
 FBC-B 1018.2. CORRIDOR WIDTH.
  
 4) SHEET A-3 FRONT COUNTER DETAIL WITH SOFFIT ABOVE,
 THE DETAIL DOE NOT PROVIDE ANCHORING OF THE SOFFIT
 FRAMING TO FRAMING MEMBERS ABOVE, TYPE OF ANCHOR, SIZE
 NOR SPACING OF ANCHORS, 2010 FBC-B TABLE 2506.2 STEEL
 STUDS NON-LOAD BEARING.
  
 5) POINT OF CONSIDERATION/ UNDER SEPERATE PERMIT: 2010
 FBC-B:
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. [F]
 EACH REQUIRED COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT
 SYSTEM REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR
 CHAPTER 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO
 HAVE A TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 904.3.2 ACTUATION. [F]
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE
 AUTOMATICALLY ACTUATED AND PROVIDED WITH A MANUAL MEANS
 OF ACTUATION IN ACCORDANCE WITH SECTION 904.11.1.
  
 904.11.1 MANUAL SYSTEM OPERATION. [F]
 A MANUAL ACTUATION DEVICE SHALL BE LOCATED AT OR NEAR A
 MEANS OF EGRESS FROM THE COOKING AREA A MINIMUM OF 10
 FEET (3048 MM) AND A MAXIMUM OF 20 FEET (6096 MM) FROM
 THE KITCHEN EXHAUST SYSTEM. THE MANUAL ACTUATION DEVICE
 SHALL BE INSTALLED NOT MORE THAN 48 INCHES (1200 MM) OR
 LESS THAN 42 INCHES (1067 MM) ABOVE THE FLOOR AND SHALL
 CLEARLY IDENTIFY THE HAZARD PROTECTED. THE MANUAL
 ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40 POUNDS
 (178 N) AND A MAXIMUM MOVEMENT OF 14 INCHES (356 MM) TO
 ACTUATE THE FIRE SUPPRESSION SYSTEM.
  
 6) SHEET M-1 A/C UNIT RACK DETAIL:
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(F)PRE-ENGINEERED A/C STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) SHEET M-2 UP-BLAST/ EXHAUST FAN DETAIL: WILL HAVE TO
 PROVIDE COMPLIANCE WITH SECTION 2010 FBC-B 1609.8
 ROOFTOP EQUIPMENT, PROVIDE DOCUMENTATION.
  
 9) SHEET M-2 ROOF CURB DETAIL DOES NOT PROVIDE
 ANCHORAGE TO THE ROOF FRAMING NOR DOES THE PLANS
 INDICATE THE TYPE OF ROOF FRAMING AND DECKING THE CURB
 WILL BE ATTACHED TOO. 2010 FBC-B 1609.8 ROOFTOP
 EQUIPMENT.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  