Plan Review Notes
Plan Review Notes For Permit 12081013
Permit Number 12081013
Review Stop B
Sequence Number 3
Notes
Date Text
2012-12-03 10:02:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. INCLUDE WIND DESIGN CRITERIA FBC 1603.1.4. PLEASE
 NOTE THAT THIS PROJECT APPEARS TO BE LOCATED IN
 EXPOSURE D.
  
 2ND REVIEW - UNABLE TO LOCATE ON RESUBMITTED DOCUMENT
 (CALCULATIONS). ALSO THE DOCUMENTS ARE PHOTOCOPIES,
 PLEASE SUBMIT ORIGINAL SIGNED SEALED ENGINEERING PER FS
 471. PLEASE STATE THE WIND DESIGN CRITERIA WHICH
 APPEARS TO BE A MINIMUM OF 170MPH EXPOSURE D.
  
  
 3RD REVIEW - PHOTOCOPIED ENGINEERING SUBMITTED. PROVIDE
 SIGNED, SEALED, DATED ORIGINALS AS REQUIRED BY FS 471.
 ALSO PROVIDE ENGINEER'S RATIONALE FOR EXPOSURE C.
 ENGINEERING SUBMITTED IS FOR PH2 AND SHOWS TWO
 DIFFERENT SIZES, THIS JOB IS FOR UNIT 26CD AND ONLY ONE
 SCREEN PROPOSED. REVISE ENGINEERING TO BE EITHER
 GENERIC OR SPECIFIC TO THIS UNIT.
  
 2-3. OK