Plan Review Notes For Permit 12081011 |
Permit Number |
12081011 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-10-18 17:18:54 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 1. INCLUDE WIND DESIGN CRITERIA FBC 1603.1.4. PLEASE | | NOTE THAT THIS PROJECT APPEARS TO BE LOCATED IN | | EXPOSURE D. | | | | UNABLE TO LOCATE ON RESUBMITTED DOCUMENT | | (CALCULATIONS). ALSO THE DOCUMENTS ARE PHOTOCOPIES, | | PLEASE SUBMIT ORIGINAL SIGNED SEALED ENGINEERING PER FS | | 471. PLEASE STATE THE WIND DESIGN CRITERIA WHICH | | APPEARS TO BE A MINIMUM OF 170MPH EXPOSURE D. | | | | 2. PROVIDE TWO SETS OF THE CURRENT NOA REFERRED TO ON | | THE PLAN (11-1117.02), FAC9N-3, FBC 1609. | | | | NOT ADDRESSED, PLEASE SUBMIT. | | | | 3. PROVIDE A PLAN WHICH SHOWS LOCATION OF PROPOSED | | IMPROVEMENT, FBC 106. | | | | TWO DIFFERENT FLOOR PLANS SUBMITTED WITH THREE PERMIT | | NUMBERS. PROVIDE TWO SETS OF PLANS FOR EACH PERMIT, | | ALONG WITH THE FLOOR PLAN SPECIFIC TO UNIT. | | | | |
|