2012-10-18 17:18:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. INCLUDE WIND DESIGN CRITERIA FBC 1603.1.4. PLEASE
 NOTE THAT THIS PROJECT APPEARS TO BE LOCATED IN
 EXPOSURE D.
  
 UNABLE TO LOCATE ON RESUBMITTED DOCUMENT
 (CALCULATIONS). ALSO THE DOCUMENTS ARE PHOTOCOPIES,
 PLEASE SUBMIT ORIGINAL SIGNED SEALED ENGINEERING PER FS
 471. PLEASE STATE THE WIND DESIGN CRITERIA WHICH
 APPEARS TO BE A MINIMUM OF 170MPH EXPOSURE D.
  
 2. PROVIDE TWO SETS OF THE CURRENT NOA REFERRED TO ON
 THE PLAN (11-1117.02), FAC9N-3, FBC 1609.
  
 NOT ADDRESSED, PLEASE SUBMIT.
  
 3. PROVIDE A PLAN WHICH SHOWS LOCATION OF PROPOSED
 IMPROVEMENT, FBC 106.
  
 TWO DIFFERENT FLOOR PLANS SUBMITTED WITH THREE PERMIT
 NUMBERS. PROVIDE TWO SETS OF PLANS FOR EACH PERMIT,
 ALONG WITH THE FLOOR PLAN SPECIFIC TO UNIT.
  
  