Plan Review Notes For Permit 12080935 |
Permit Number |
12080935 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-09-17 12:50:38 | PROVIDE ELECTRICAL SIGN DETAIL SHOWING REQUIRED | | DISCONNECTS AND CIRCUIT SIZE. DISCONNECTS ARE REQUIRED | | WITHIN SIGHT OF THE SIGN FACE AND SIGN CONTROLLER. NEC | | 600.6 | | | | VERIFY AND INDICATE ON THE PLANS THAT THE SIGN HAS A | | LISTING BY A NATIONALLY RECOGNIZED TESTING LABORATORY. | | NEC 110.3, 600.3 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|