Plan Review Notes For Permit 12080898 |
Permit Number |
12080898 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-08-30 12:20:24 | 550 SOUTH ROSEMARY AVE. SUTE #119 | | PERMIT #12080898 | | | | | | FIRE DEPARTMENT REVIEW COMMENTS | | | | * THE CORRECT ADDRESS MUST APPEAR ON THE PERMIT | | APPLICATION INCLUDING THE (SUITE NUMBER). | | | | * NOTE ALL POSSIBLE OBSTRUCTIONS OF BEAMS AND LIGHTING | | THAT MAYBE OBSTRUCTING SPRINKLER PROTECTION. | | | | * THE ARCHITECTUAL DRAWING INDICATE A LACK OF SPRINKLER | | COVERAGE/OBSTRUCTIONS AROUND THE BOX BEAMS, IN THE MAIN | | DINING AREA, POSSIBLY ADDITIONAL SPRINKLER COVERAGE | | REQUIRED. | | | | |
|