Plan Review Notes For Permit 12080821 |
Permit Number |
12080821 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-12-14 13:53:43 | *** CORRECTIONS NEEDED TO MECHANICAL *** | | | | 1) SEE BUILDING REVIEW NOTE #1 REGARDING ENERGY CAL'S. | | PLEASE CORRECT REGARDING SIGNED & DATED BY OWNER/AGENT, | | SEE LINE 14 E-CAL'S. WATER HEATER AND YELLOW HIGH | | LIGHTS ON SUBMITTED ENERGY CAL'S. PLEASE CORRECT, PER | | 2010 FBC/ENERGY 103.2.3.2 & 103.33 | | | | 2) MECHANICAL PERMIT # 12080823 WAS APPLIED FOR AND | | COOLING LOAD CAL'S. WITH DUCT CALCULATIONS WAS | | SUBMITTED, BUT NO MECHANICAL PLAN WAS SUBMITTED. PLEASE | | SUBMIT MECHANICAL PLANS WITH ALL PERTINENT INFORMATION | | ON THEM, PER 2010 WPB AMEND. 107.3.5.3 (10). | | | | *** MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD | | INC.) | | *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|