Plan Review Notes
Plan Review Notes For Permit 12080821
Permit Number 12080821
Review Stop B
Sequence Number 2
Notes
Date Text
2012-12-06 14:01:52RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED (SEC. 103.2 OF
 2010 FBC-ENERGY CONSERVATION). COORDINATE ALL THE
 INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED:
 (NOTE: SEE SEC. 101.4.3 OF 2010 FBC-ENERGY
 CONSERVATION. COMPLIANCE CAN BE ACHIEVED FOR THE
 ADDITION ALONE OR FOR ENTIRE BUILDING).
  
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM.
  
 B) SPECIFY ALL WALL TYPES AS SHOWN ON PLANS. THERE ARE
 NOT CONCRETE BLOCK WALLS. SEE PLANS. AND PROPERTY
 APPRAISAL SAYS WOOD FRAME STUCCO/HOLLOW TILE.
  
 C) SPECIFY ALL CEILING TYPES AS SHOWN ON PLANS.
  
 D) CLARIFY WHY THE EF VALUE FOR THE HOT WATER SYSTEM IS
 "0".
  
 E) CLEARLY PROVIDE THE NAME OF PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. 405.4.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 F) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM.
  
 G) ROOF SPECIFICATION ON SHEET 2 OF 6 TO MATCH PLANS.
 THERE ARE FLAT ROOFS AND ACCORDING TO CITY RECORDS THEY
 HAVE CLAY TILE NOT FLAT CONCRETE TILE.
  
 H) REVISE THE ATTIC INFORMATION ON SHEET 2 OF 6. THERE
 ARE VENTED AND UNVENTED ATTICS.
  
 I) REVISE WALL ON SHEET 3 OF 6. THERE ARE MASONRY WALLS
 AND FRAMED WALLS.
  
 J) THERE ARE NO WOOD DOORS. SEE PLANS AND PRODUCT
 APPROVALS SUBMITTED. REVISE PAGE 3 OF 6.
  
 2- FLAT ROOF NOA 12-0227.18 SUBMITTED. A) SELECTED
 ASSEMBLY ON PAGE 6 OF 7 IS FOR AN INSULATED ASSEMBLY.
 ARCHITECTURAL PLANS DON'T SPECIFY INSULATED ASSEMBLY.
 COORDINATE WITH ARCHITECT AND REVISE AS REQUIRED.
 (REPEAT COMMENT. ARCHITECT IS NOT SPECIFYING INSULATED
 ASSEMBLY AS SHOWN ON NOA SUBMITTED).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR FRENCH DOORS AS SHOWN ON PLANS.
 INCLUDING FRENCH DOORS WITH SIDELITES AS SHOWN ON
 PLANS.
 ***RESPONSE: NOA 11-1025.02 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD
 CURRENT NOA. RESUBMIT.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. (REPEAT
 COMMENT).
 ***RESPONSE: ONLY THE SIMPSON STRUCTURAL CONNECTORS
 WERE APPROVED BY THE ENGINEER. ALL THE PRODUCT
 APPROVALS NEED TO BE REVIEWED AND APPROVED.
  