2012-12-06 14:01:52 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| REVIEW COMMENTS |
| CODE: 2010 FBC. |
| |
| 1- REVISE ENERGY CALCULATIONS SUBMITTED (SEC. 103.2 OF |
| 2010 FBC-ENERGY CONSERVATION). COORDINATE ALL THE |
| INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED: |
| (NOTE: SEE SEC. 101.4.3 OF 2010 FBC-ENERGY |
| CONSERVATION. COMPLIANCE CAN BE ACHIEVED FOR THE |
| ADDITION ALONE OR FOR ENTIRE BUILDING). |
| |
| A) COMPLETE ALL THE INFORMATION ON TOP OF FORM. |
| |
| B) SPECIFY ALL WALL TYPES AS SHOWN ON PLANS. THERE ARE |
| NOT CONCRETE BLOCK WALLS. SEE PLANS. AND PROPERTY |
| APPRAISAL SAYS WOOD FRAME STUCCO/HOLLOW TILE. |
| |
| C) SPECIFY ALL CEILING TYPES AS SHOWN ON PLANS. |
| |
| D) CLARIFY WHY THE EF VALUE FOR THE HOT WATER SYSTEM IS |
| "0". |
| |
| E) CLEARLY PROVIDE THE NAME OF PERSON DOING THE |
| CALCULATIONS AS REQUIRED BY SEC. 405.4.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| F) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. |
| |
| G) ROOF SPECIFICATION ON SHEET 2 OF 6 TO MATCH PLANS. |
| THERE ARE FLAT ROOFS AND ACCORDING TO CITY RECORDS THEY |
| HAVE CLAY TILE NOT FLAT CONCRETE TILE. |
| |
| H) REVISE THE ATTIC INFORMATION ON SHEET 2 OF 6. THERE |
| ARE VENTED AND UNVENTED ATTICS. |
| |
| I) REVISE WALL ON SHEET 3 OF 6. THERE ARE MASONRY WALLS |
| AND FRAMED WALLS. |
| |
| J) THERE ARE NO WOOD DOORS. SEE PLANS AND PRODUCT |
| APPROVALS SUBMITTED. REVISE PAGE 3 OF 6. |
| |
| 2- FLAT ROOF NOA 12-0227.18 SUBMITTED. A) SELECTED |
| ASSEMBLY ON PAGE 6 OF 7 IS FOR AN INSULATED ASSEMBLY. |
| ARCHITECTURAL PLANS DON'T SPECIFY INSULATED ASSEMBLY. |
| COORDINATE WITH ARCHITECT AND REVISE AS REQUIRED. |
| (REPEAT COMMENT. ARCHITECT IS NOT SPECIFYING INSULATED |
| ASSEMBLY AS SHOWN ON NOA SUBMITTED). |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR FRENCH DOORS AS SHOWN ON PLANS. |
| INCLUDING FRENCH DOORS WITH SIDELITES AS SHOWN ON |
| PLANS. |
| ***RESPONSE: NOA 11-1025.02 SUBMITTED WAS SUPERSEDED BY |
| MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD |
| CURRENT NOA. RESUBMIT. |
| |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. (REPEAT |
| COMMENT). |
| ***RESPONSE: ONLY THE SIMPSON STRUCTURAL CONNECTORS |
| WERE APPROVED BY THE ENGINEER. ALL THE PRODUCT |
| APPROVALS NEED TO BE REVIEWED AND APPROVED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |