2012-09-27 11:23:58RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. MAKE SURE ALL THE
 INFORMATION IS COMPLETED AND SIGNED BY ALL PARTIES AT
 THE BOTTOM OF THE FORM. SEC. 103.2.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- STORM PANELS NOA 10-0222.03 SUBMITTED: PROVIDE
 COMPLETE INSTALLATION SCHEDULE TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL. CLEARLY IDENTIFY SPECIFIC SHUTTERS
 MOUNTING CONDITION AND ANCHOR TYPE AND SPACING TO BE
 USED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
 ***NOTE: CLARIFY WHY SUBMITTING STORM SHUTTERS PRODUCT
 APPROVAL. ARE ALL THE WINDOWS AND DOORS IMPACT
 RESISTANT?
  
 4- FLAT ROOF NOA 12-0227.18 SUBMITTED. A) SELECTED
 ASSEMBLY ON PAGE 6 OF 7 IS FOR AN INSULATED ASSEMBLY.
 ARCHITECTURAL PLANS DON'T SPECIFY INSULATED ASSEMBLY.
 COORDINATE WITH ARCHITECT AND REVISE AS REQUIRED.
  
 B) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR FRENCH DOORS AS SHOWN ON PLANS.
 INCLUDING FRENCH DOORS WITH SIDELITES AS SHOWN ON
 PLANS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS.
  
 7- SHEET A3: PROPOSED 2ND FLOOR PLAN SHOWS NEW ATTIC
 ACCESS. IT LOOKS LIKE IT'S NOT READILY ACCESSIBLE AS
 REQUIRED BY SEC. R807. REVISE AS REQUIRED AND PROVIDE
 DIMENSIONS.
 ***NOTE: THERE IS A NOTE THAT THE AHU IS LOCATED HERE.
 VERIFY THAT AIR HANDLER UNIT WILL BE OK IN THIS
 LOCATION. CHECK ACCESS AND REQUIRED CLEARANCES TO
 SERVICE THE EQUIPMENT.
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4.
  
 9- PROVIDE COMPLETE SPECIFICATIONS FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- A) ENGINEER TO REVISE ALL THE ROOF SHEATHING
 DETAILS AND SPECIFICATIONS. NEED TO SPECIFY MIN. 8D
 RING SHANK NAILS (NOT 10D) AS REQUIRED BY SEC.
 R803.2.3.1 AND ALSO NEED TO SPECIFY NAILS AT 4"O.C. IN
 ROOF ZONE #3.
  
 B) ARCHITECT TO REVISE ROOF SHEATHING NAILING
 SPECIFICATIONS SHOWN ON ALL THE WALL SECTIONS AND
 DETAILS TO MATCH REVISED ENGINEER SPECIFICATIONS.
 COORDINATE WITH ITEM 10(A) ABOVE. SEC. 107.2.1 CITY
 AMENDMENTS.
  