2012-10-15 13:31:58REVISION REQUIRED
  
 1) SPECIFY WHICH ONE OF THE ASSEMBLIES FROM THE
 HYDRO-STOP PREMIUM COAT SYSTEM PRODUCT APPROVAL THAT
 WAS SUBMITTED WILL BE INSTALLED. ALL THREE OF THE
 ASSEMBLIES REQUIRE A MECHANICALLY FASTENED INSULATION
 BASE LAYER TO WHICH THE PREMIUM COAT SYSTEM IS APPLIED.
 THE MAXIMUM DESIGN PRESSURE LISTED IN THE NOA IS -60
 PSF WHICH DOES NOT MEET THE HIGHER UPLIFT PRESSURES AT
 THE PERIMETER AND CORNER AREAS. THE STRUCTURE IS
 LOCATED IN 170 MPH VULT / 132 VASD EXPOSURE C PER FBC
 R301.2.1.4. PLEASE SUBMIT 2 SETS OF RAS 117
 CALCULATIONS FOR THE ENHANCED FASTENING OF THE
 INSULATION THAT HAVE BEEN SIGNED AND SEALED BY A
 FLORIDA ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT AS REQUIRED BY LIMITATION NUMBER 7.
 FBCR301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714