Plan Review Notes For Permit 12080740 |
Permit Number |
12080740 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-10-03 16:51:44 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS | | REQUIRED BY FBCR M1401.3 | | | | 2) SUBMIT TWO SETS OF MECHANICAL PLANS WITH THE | | LOCATIONS AND SIZES OF ALL SUPPLY AND RETURN DUCTS | | SPECIFIED. SPECIFY THE GRILL SIZES FOR THE SUPPLIES AND | | RETURNS AND THE CFMS FOR EACH OF THE SUPPLY OUTLETS. | | CITY AMENDMENTS 107.3.5.3 | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT IS | | COORDINATED WITH THE SIZING CALCULATIONS. FBCR M1401.3 | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | RETURN AIR REQUIREMENTS ON THE PLANS. | | | | 5) SHOW THE LOCATION OF ALL HVAC EQUIPMENT ON THE | | PLANS. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|