Plan Review Notes
Plan Review Notes For Permit 12080740
Permit Number 12080740
Review Stop E
Sequence Number 1
Notes
Date Text
2012-08-27 14:32:5712080740
 309 DIVISION AVE
 RESIDENTIAL RENOVATION
  
 PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH WIRE SIZES,
 GROUNDING ETC. NEC 215.15
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. 2010 FBC R314,
 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  