2012-10-04 12:11:13THE SCOPE OF WORK PROVIDED IS INCOMPLETE. THE
 ELECTRICAL PERMIT , PLUMBING PERMIT AND BUILDING PERMIT
 APPLICATIONS ARE ALL DIFFERENT. PLEASE PROVIDE AN
 ELECTRICAL PLAN OR CLARIFY THE SCOPE OF THE WORK
 PROPOSED ON A SEPERATE DOCUMENT SIGNED BY THE
 CONTRACTOR (CGC).
  
 INDICATE THE SIZE OF THE WATER HEATERS AND SIZE OF THE
 ELECTRICAL CIRCUIT REQUIRED FOR THE NEW IN LINE
 HEATERS. NEC 240.4
  
 VERIFY THE EXISTING ELECTRICIAL SERVICE HAS THE
 CAPACITY FOR EIGHT ADDITIONAL IN LINE WATER HEATING
 LOADS. NEC 220.40
  
  