Plan Review Notes For Permit 12080732 |
Permit Number |
12080732 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-10-04 12:11:13 | THE SCOPE OF WORK PROVIDED IS INCOMPLETE. THE | | ELECTRICAL PERMIT , PLUMBING PERMIT AND BUILDING PERMIT | | APPLICATIONS ARE ALL DIFFERENT. PLEASE PROVIDE AN | | ELECTRICAL PLAN OR CLARIFY THE SCOPE OF THE WORK | | PROPOSED ON A SEPERATE DOCUMENT SIGNED BY THE | | CONTRACTOR (CGC). | | | | INDICATE THE SIZE OF THE WATER HEATERS AND SIZE OF THE | | ELECTRICAL CIRCUIT REQUIRED FOR THE NEW IN LINE | | HEATERS. NEC 240.4 | | | | VERIFY THE EXISTING ELECTRICIAL SERVICE HAS THE | | CAPACITY FOR EIGHT ADDITIONAL IN LINE WATER HEATING | | LOADS. NEC 220.40 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|