Plan Review Notes
Plan Review Notes For Permit 12080707
Permit Number 12080707
Review Stop E
Sequence Number 1
Notes
Date Text
2012-08-27 10:29:3612080707
 700 S. ROSEMARY AVENUE # 100
 MELLOW YELLOW BUILD OUT
  
 PLEASE CLARIFY THE ELECTRICAL RISER PLAN AS NOTED.
  
 DISTRIBUTION PANEL ?LDP? AND PANEL ?LP1? MAY BE
 MISLABELED. NEC 215.5
  
 ?LP1 / LDP? REQUIRE A MAIN BREAKER. NEC 408.36
  
 INDICATE THE SIZE OF THE XFMR. PROVIDE LINE AND LOAD
 FEEDER CONDUCTOR SIZES. NEC 215.5
  