Plan Review Notes For Permit 12080707 |
Permit Number |
12080707 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-08-27 10:29:36 | 12080707 | | 700 S. ROSEMARY AVENUE # 100 | | MELLOW YELLOW BUILD OUT | | | | PLEASE CLARIFY THE ELECTRICAL RISER PLAN AS NOTED. | | | | DISTRIBUTION PANEL ?LDP? AND PANEL ?LP1? MAY BE | | MISLABELED. NEC 215.5 | | | | ?LP1 / LDP? REQUIRE A MAIN BREAKER. NEC 408.36 | | | | INDICATE THE SIZE OF THE XFMR. PROVIDE LINE AND LOAD | | FEEDER CONDUCTOR SIZES. NEC 215.5 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|