Plan Review Notes For Permit 12080616 |
Permit Number |
12080616 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-10-05 13:27:52 | 6751 NORTH JOG ROAD | | PERMIT #12080616 | | MASTER #12080469 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | THE LIFE SAFETY PLAN FROM MASTER PERMIT #12080894 | | INDICATES THE VISITOR CENTER TO BE AN ASSEMBLY | | OCCUPANCY WITH AN OCCUPANT LOAD OF 544 PERSONS. PROVIDE | | SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW ASSEMBLY | | OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300 | | OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY | | VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. REFERENCE | | SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE ? | | NFPA 101 | | | | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE | | NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN | | THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE | | BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. | | | | PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW | | SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO | | THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER | | ACTIVATES IN THE ELEVATOR MACHINE ROOM. | | | | PROVIDE TAMPER SWITCH FOR YARD POST INDICATOR VALVE | | (PIV). | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | (561) 805-6730 | | [email protected] |
|