2012-08-20 09:21:3912080493
 255 WALTON BLVD.
 APARTMENT RENOVATION
  
 THE PLANS ARE UNCLEAR AS TO THE SCOPE OF THE ELECTRICAL
 WORK. PLEASE PROVIDE THE FOLLOWING INFORMATION:
  
 IDENTIFY ON THE PLAN WHAT PORTION OF THE ELECTRICAL
 SYSTEM WILL BE UNDER GOING RENOVATION AND WHAT PORTION
 WILL REMAIN AS EXISTING. NEC 215.5
  
 REMODELING OF AN EXISTING STRUCTURE WITH SLEEPING AREAS
 IS REQUIRED TO INCLUDE INTERCONNECTED SMOKE DETECTORS.
 IF THE STRUCTURE HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315, 210 FBC 916.1, FBC EXISTING BUILDING
 704.4.3
  
  
 ROBERT LECKY
 PLANS EXAMINER
 [email protected]
 561-805-6718
  
  