2012-08-30 15:00:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A SITE PLAN SHOWING PROPOSED LOCATION AND
 DISTANCE TO PROPERTY LINE, FBC 705.2.
  
 2. PLANS SPECIFY "STRAPS" "POST ANCHOR" AND "BUCKET" -
 SEE FAC9N-3, PRODUCT APPROVAL REQUIRED FOR STRUCTURAL
 CONNECTORS, AND ALL ELEMENTS TO BE SPECIFIED TO SHOW
 RESISTANCE TO WIND LOADS FBC 1609, FBC 107.2.1. "STRAP"
 AND "BUCKET" TO BE SPECIFIC TO A CONNECTOR WHICH CAN
 RESIST THE SPECIFIED DESIGN LOADS, PLEASE REVISE PLAN
 TO INCLUDE INFORMATION AND PROVIDE PRODUCT APPROVAL.
  
 3. SPANS, OVERALL DIMENSIONS NOT SHOWN, SPACING OF
 POSTS, CONNECTION OF LEDGER AND SUBSTRATE, CONNECTION
 OF POST TO BLOCK WALL, BLOCK WALL CONSTRUCTION, RAFTER
 PITER PITCH, ROOF PITCH, ROOF COVERING, NOT SHOWN FBC
 107.2.1, FBC 1609.
  
 4. INCLUDE A CODE SUMMARY - BUILDING TYPE FBC CHAPTER
 6, OCCUPANCY CLASSIFICATION, FBC CHAPTER 3, BUILDING
 SQUARE FOOT AREA.
  
 5. PLAN SHOWS A RAFTER SUPPORTED BY ANOTHER RAFTER, NOT
 CLEAR HOW THIS IS CONNECTED AND HOW THIS WILL RESIST
 WIND AND GRAVITY LOADS, FBC 1609, FBC 107.2.1.
  
 6. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC
 1603.1.4.
  
 IF PLANS ARE NOT SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL LICENSED UNDER FS471 OR FS481 (ENGINEER OR
 ARCHITECT), PLEASE ADDRESS THE FOLLOWING:
  
 7. SEE FBC 1609.1.1, DESIGN IS TO BE IN ACCORDANCE WITH
 ASCE7-10. PROVIDE CALCULATIONS TO SHOW HOW SPANS,
 CONNECTORS, COLUMNS, POST SIZE, RAFTER SIZE, ETC. HAVE
 BEEN DETERMINED.
  