Plan Review Notes
Plan Review Notes For Permit 12080469
Permit Number 12080469
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-11-30 15:39:516751 NORTH JOG ROAD
 PERMIT #12080469
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PEDESTRIAN BRIDGE - RESPONSE: UPON FURTHER CODE REVIEW,
 THE FLORIDA FIRE PREVENTION CODE REQUIRES (EVEN WHILE
 THE FBC MAY NOT) THE FOLLOWING WITHOUT EXCEPTION:
 NFPA 101 SECTION 7.2.4.3.1 "FIRE BARRIERS SEPARATING
 BUILDINGS OR AREAS BETWEEN WHICH THERE ARE HORIZONTAL
 EXITS SHALL HAVE A MINIMUM 2-HOUR FIRE RESISTANCE
 RATING, UNLESS OTHERWISE PROVIDED IN 7.2.4.4.1, AND
 SHALL
 PROVIDE A SEPARATION THAT IS CONTINUOUS TO THE FINISHED
 GROUND LEVEL." ALSO NFPA 101 SECTION 7.2.4.4 "BRIDGES
 SERVING HORIZONTAL EXITS BETWEEN BUILDINGS. THE
 PROVISIONS OF 7.2.4.4 SHALL APPLY TO BRIDGES SERVING
 HORIZONTAL EXITS BETWEEN BUILDINGS AND TO THE
 ASSOCIATED HORIZONTAL EXIT FIRE BARRIER. THE MINIMUM
 2-HOUR FIRE RESISTANCE-RATED BARRIER REQUIRED BY
 7.2.4.3.1 SHALL EXTEND AS FOLLOWS:
 (1) VERTICALLY FROM THE GROUND TO A POINT 10 FEET ABOVE
 THE BRIDGE OR TO THE ROOFLINE, WHICHEVER IS LOWER
 (2) HORIZONTALLY FOR NOT LESS THAN 10 FEET TO EACH SIDE
 OF THE BRIDGE 7.2.4.4.2 ANY OPENING IN THE FIRE BARRIER
 ADDRESSED IN 7.2.4.4.1 SHALL BE PROTECTED WITH FIRE
 DOOR ASSEMBLIES OR FIXED FIRE WINDOW ASSEMBLIES HAVING
 A 3/4-HOUR FIRE PROTECTION RATING, UNLESS OTHERWISE
 PROVIDED IN 7.2.4.4.3."
  
 SHEET 710-A5-100 - NEW COMMENT: THE SOUTH LOBBY DOOR
 SWING WAS REVISED AND NOW THE SWING IS AGAINST THE FLOW
 OF EGRESS.
  
 SHEET 710-FP-100 - RESPONSE: THE EXCEPTION STATED IN
 FBC 1004.1.1 FOR REDUCING THE OCCUPANT LOAD IS NOT
 APPROVED BY THE FIRE MARSHAL'S OFFICE.
 ORIGINAL COMMENT: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 SHEET 710-FP-100 - REPEAT COMMENT: PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
  
 SHEET 710-FP-111 - RESPONSE: THE RESPONSE LETTER
 INDICATES HYDRAULIC CALCULATIONS WERE SUBMITTED WITH
 THE ORIGINAL SUBMITTAL AND ALSO WITH THE RE-SUBMITTAL;
 HOWEVER, A FILE CONTAINING THESE CALCULATIONS CANNOT BE
 LOCATED.
 ORIGINAL COMMENT: SUBMIT HYDRAULIC CALCULATIONS FOR
 REVIEW.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]