Plan Review Notes
Plan Review Notes For Permit 12080469
Permit Number 12080469
Review Stop P
Sequence Number 1
Notes
Date Text
2012-08-22 11:54:46FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A1-102, A1-201
 THE DETAIL FOR THE STANDARD TOILET STALLS DOES NOT HAVE
 A MEASUREMENT FOR STALL DEPTH ON THE DRAWING. THE
 INSIDE DIMENSION APPEARS TO BE 4'-6". THE MINIMUM FOR
 STALLS IS 60" DEEP. FBC PLUMBING 405.3.1
  
 2. AS THREE FLOORS ARE OCCUPIED AND AN AGGREGATE OF
 MORE THAN SIX WATER CLOSETS ARE REQUIRED, A UNISEX
 RESTROOM WILL BE REQUIRED. THE RESTROOM SHOULD BE
 PLACED ON THE SECOND FLOOR TO BE WITHIN ONE FLOOR LEVEL
 PER 403.3.2. THE UNISEX FIXTURES COUNT AS REQUIRED
 FIXTURES.
 403.5 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT.
  
 3. SHEET PB-106
 THE SANITARY DRAINAGE FROM THE SECOND FLOOR RESTROOMS
 IS DROPPING INTO THE VENT FOR THE FIRST FLOOR
 RESTROOMS.
 908.1 INDIVIDUAL VENT AS COMMON VENT.
 AN INDIVIDUAL VENT IS PERMITTED TO VENT TWO TRAPS OR
 TRAPPED FIXTURES AS A COMMON VENT. THE TRAPS OR TRAPPED
 FIXTURES BEING COMMON VENTED SHALL BE LOCATED ON THE
 SAME FLOOR LEVEL.
  
 4. A CLEANOUT WILL BE REQUIRED NEAR THE BASE OF THE
 SOIL STACK FOR THE SECOND FLOOR RESTROOMS.
 708.3.4 BASE OF STACK.
 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE
 OR SOIL STACK.
  
 5, ALL HOSE BIBBS AND WALL HYDRANTS REQUIRE A SEPARATE
 SHUTOFF VALVE.
 606.2 LOCATION OF SHUTOFF VALVES.
 SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER THAN
 ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 6. SHEET PB-106
 THE DOWNFEED WATER RISERS FOR THE FIRST FLOOR REQUIRE
 SHUTOFF VALVES.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN
 OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 7. A SERVICE SINK WAS NOT FOUND ON THE PLAN.
 403.1 ASSEMBLY OCCUPANCIES REQUIRE A SERVICE SINK.
  
 8. SHEET PB-102
 A. A SHUTOFF VALVE IS REQUIRED WHERE THE DOMESTIC WATER
 ENTERS THE BUILDING. 606.1 (2)
 B. A BACKFLOW PREVENTOR IS SHOWN INSIDE THE BUILDING.
 IF THIS IS THE MAIN RPZ BACKFLOW FOR THE BUILDING, IT
 SHOULD BE AS CLOSE TO THE DOMESTIC WATER METER AS
 POSSIBLE PER UTILITIES ORD.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  
  
  
  
  
  
  