2012-08-22 11:54:46 | FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. SHEET A1-102, A1-201 |
| THE DETAIL FOR THE STANDARD TOILET STALLS DOES NOT HAVE |
| A MEASUREMENT FOR STALL DEPTH ON THE DRAWING. THE |
| INSIDE DIMENSION APPEARS TO BE 4'-6". THE MINIMUM FOR |
| STALLS IS 60" DEEP. FBC PLUMBING 405.3.1 |
| |
| 2. AS THREE FLOORS ARE OCCUPIED AND AN AGGREGATE OF |
| MORE THAN SIX WATER CLOSETS ARE REQUIRED, A UNISEX |
| RESTROOM WILL BE REQUIRED. THE RESTROOM SHOULD BE |
| PLACED ON THE SECOND FLOOR TO BE WITHIN ONE FLOOR LEVEL |
| PER 403.3.2. THE UNISEX FIXTURES COUNT AS REQUIRED |
| FIXTURES. |
| 403.5 UNISEX TOILET AND BATHING ROOMS. |
| IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE |
| UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE |
| OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS |
| REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE |
| WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE |
| OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET |
| ROOM REQUIREMENT. |
| |
| 3. SHEET PB-106 |
| THE SANITARY DRAINAGE FROM THE SECOND FLOOR RESTROOMS |
| IS DROPPING INTO THE VENT FOR THE FIRST FLOOR |
| RESTROOMS. |
| 908.1 INDIVIDUAL VENT AS COMMON VENT. |
| AN INDIVIDUAL VENT IS PERMITTED TO VENT TWO TRAPS OR |
| TRAPPED FIXTURES AS A COMMON VENT. THE TRAPS OR TRAPPED |
| FIXTURES BEING COMMON VENTED SHALL BE LOCATED ON THE |
| SAME FLOOR LEVEL. |
| |
| 4. A CLEANOUT WILL BE REQUIRED NEAR THE BASE OF THE |
| SOIL STACK FOR THE SECOND FLOOR RESTROOMS. |
| 708.3.4 BASE OF STACK. |
| A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE |
| OR SOIL STACK. |
| |
| 5, ALL HOSE BIBBS AND WALL HYDRANTS REQUIRE A SEPARATE |
| SHUTOFF VALVE. |
| 606.2 LOCATION OF SHUTOFF VALVES. |
| SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER THAN |
| ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| |
| 6. SHEET PB-106 |
| THE DOWNFEED WATER RISERS FOR THE FIRST FLOOR REQUIRE |
| SHUTOFF VALVES. |
| 606.1 LOCATION OF FULL-OPEN VALVES. |
| FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN |
| OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL |
| OCCUPANCIES. |
| |
| 7. A SERVICE SINK WAS NOT FOUND ON THE PLAN. |
| 403.1 ASSEMBLY OCCUPANCIES REQUIRE A SERVICE SINK. |
| |
| 8. SHEET PB-102 |
| A. A SHUTOFF VALVE IS REQUIRED WHERE THE DOMESTIC WATER |
| ENTERS THE BUILDING. 606.1 (2) |
| B. A BACKFLOW PREVENTOR IS SHOWN INSIDE THE BUILDING. |
| IF THIS IS THE MAIN RPZ BACKFLOW FOR THE BUILDING, IT |
| SHOULD BE AS CLOSE TO THE DOMESTIC WATER METER AS |
| POSSIBLE PER UTILITIES ORD. |
| |