2012-10-04 17:02:46 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2010 | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PAGE HC-101: PLAN SHOWS DUCT PENETRATIONS OF THE | | STAIR EXIT ENCLOSURE. SUCH PENETRATIONS AND VENTILATION | | SYSTEMS ARE PROHIBITED FOR EXIT ENCLOSURES PER FBC-B | | 1022.4 AND 1022.5. | | | | 2. PAGE HC-101: PLAN SHOWS SEVERAL DUCT PENETRATIONS | | FROM THE FIRST FLOOR UP THROUGH TO THE 2ND FLOOR. SHOW | | HOW THESE PENETRATIONS ARE TO BE PROTECTED PER FBC-M | | 607.5. | | | | 3. PAGE HC-102: PLAN SHOWS DUCT PENETRATIONS OF THE | | STAIR EXIT ENCLOSURE. SUCH PENETRATIONS AND VENTILATION | | SYSTEMS ARE PROHIBITED FOR EXIT ENCLOSURES PER FBC-B | | 1022.4 AND 1022.5. | | | | 4. PAGE HC-103: PLAN SHOWS AHU/VENTILATION SYSTEM FOR | | THE STAIR EXIT ENCLOSURE AND THE REST OF THE 3RD FLOOR | | LOCATED IN THE EXIT ENCLOSURE. THE VENTILATION SYSTEM | | FOR THE EXIT ENCLOSURE MUST BE DEDICATED TO THE | | ENCLOSURE PER FBC-B 1022.5. | | | | 5. PAGE HC-103: DUCT PENETRATIONS OF EXIT ENCLOSURE ARE | | PROHIBITED PER FBC--B 1022.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|