Plan Review Notes For Permit 12080469 |
Permit Number |
12080469 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-09-05 13:24:10 | THE FOLLOWING NOTES HAVE BEEN APPLIED TO THE ELECTRONIC | | PLAN. | | | | SEPARATE PERMITS ARE REQUIRED FOR THE PHOTOVOLTAIC | | SYSTEM AND SITE LIGHTING. FBC 105.1 | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | GFCI PROTECTION. NEC 422.52 | | RECEPTACLES IN ELEVATOR MACHINE ROOMS SHALL HAVE GROUND | | FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 620.85 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|