2012-09-11 15:32:51 | BUILDING PLAN REVIEW |
| PERMIT: 112080469 |
| ADD: 6751 N JOG ROAD |
| CONT: CDM CONSTRUCTORS |
| TEL: (561)689-3336 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| SEPT. 11/2012 |
| ACTION: DENIED |
| |
| 1) SHEET710- A1-300 THIRD STORY ROOF TOP GARDEN AREA, |
| TO DATE THE PLANS ONLY SHOW ONE MEANS OF EGRASS FROM |
| THE 3RD STORY ROOFTOP GARDEN, PLEASE REVIEW SECTION |
| 2010 FBC-B TABLE 1021.2 FOR ASSEMBLY OCCUPANCIES AND |
| SINGLE EXIT. |
| |
| 2) THIS SAME SHEET A1-300 INDICATES A SKYBRIDEGE TO THE |
| POWER BLOCK, SHEET 710-SS-103 ALSO MKES REFERENECE TO |
| THE SKYBRIDGE AND A NOTE INDICATEING SEE SHEET |
| 710-S3-301 FOR WIND LOADING ON SKYBRIDGE AND SKYBRIDGE |
| STAIR TOWER. THIS SHEET IS NOT INCLUDED IN THIS |
| SUBMITION, AT THIS TIME WE CAN ONLY VIEW THIS AREA AS A |
| SINGLE EXIT FROM THE THIRD FLOOR. |
| |
| 3) SHEET 710-A1-300 INDICATES THE USE OF A SKYBRIDGE TO |
| THE POWER BLOCK, PLESE REVIEW 2010 FBC-B 3104.2 |
| SEPERATE STRUCTURES, 3104.3 CONSTRUCTION, 3104.4 |
| CONTENTS & 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN |
| WALKWAYS AND BUILDINGS. |
| |
| 4) SHEET 710-A1-300 THE EAST STAIR TOWER HAS TWO |
| ISSUES: |
| 4A) THE MECHANICAL ROOM IS NOT SEPERATED FROM THE |
| VERTICAL EXIT ENCLOSURE BY A ONE HOUR RATED WALL PER |
| 2010 FBC-B 1022.1. |
| |
| 4B) THE VERTICAL EXIT ALSO HAS A/C DUCTWORK WITHIN THE |
| EXIT ENCLOSURE THAT IS COMMON TO THE THIRD FLOOR. |
| PLEASE REVIEW 2010 FBC-B 1022.4. 1022.5 EXIT ENCLOSURE |
| VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER |
| BUILDING VENTILATION SYSTEMS. |
| |
| 5) SHEET 710-A1-303 IS MISSING FIRE DAMPER, PLEASE |
| REVIEW 2010 FBC-B 1022.4. 1022.5 EXIT ENCLOSURE |
| VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER |
| BUILDING VENTILATION SYSTEMS. |
| |
| 6) EAST STAIR TOWER SHEET 710-A1-203 PLEASE PROVIDE |
| ADDITIONAL INFORMATION REQUIRED FOR SUSPENDED ACCENT |
| CANOPY, 2010 FBC-B TABLE 803.9 INTERIOR WALL & CEILING |
| FINISHES. |
| |
| 7) PLEASE REVIEW BUILDING PROJECT SUMMARY OCCUPANT |
| LOADS FOR THE SECOND FLOOR INDICATE A OCCUPANT LOAD OF |
| 25, WHEREAS THE CONFERENCE ROOM IS 533/ 15=37 |
| AND TRAIN/ WORK ROOM 1134/50= 23 OCCUPANTS OR A TOTAL |
| LOAD OF 59.TABLE 1004.1.1. |
| |
| 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 9) NO PRODUCT APPROVALS WERE SUBMITTED AT THIS TIME. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |