Plan Review Notes For Permit 12080340 |
Permit Number |
12080340 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-08-15 12:39:16 | REVISION DENIED BY MECHANICAL | | | | 1) SUBMIT REVISED ENERGY CALCULATIONS AND EQUIPMENT | | SIZING CALCULATIONS THAT CORRESPOND WITH THREE SYSTEMS | | SHOWN ON THE REVISED PLANS. FBC R M1401.3 AND 2007 FBC | | ENERGY GLITCH AMENDMENTS N1100.0.3. | | | | 2) SPECIFY THE SIZE OF THE DUCT SUPPLYING THE | | DISTRIBUTION BOX FOR THE TWO 1ST FLOOR BEDROOMS. CITY | | AMENDMENTS 107.2.1 & 107.3.5.3 | | | | 3) IDENTIFY EACH OF THE THREE SYSTEMS SHOWN ON THE | | PLANS BY LABELING THE CONDENSING UNITS AND THE | | CORRESPONDING AIR HANDLER (IE. CU 1, A/H1, ETC.). CITY | | AMENDMENTS 107.2.1 | | | | 4) SPECIFY THE TOTAL BTU CAPACITIES FOR EACH SYSTEM | | WITH THE EQUIPMENT SPECIFICATIONS. CITY AMENDMENTS | | 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|