Plan Review Notes
Plan Review Notes For Permit 12080323
Permit Number 12080323
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-08-30 13:38:431801 PALM BEACH LAKES BOULEVARD
 PERMIT #12080323
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE QUANTITY, CONSTRUCTION TYPE AND LOCATION
 OF ANY TEMPORARY OFFICES, TRAILERS OR SHEDS. SEPARATION
 DISTANCES BETWEEN BUILDINGS UNDER CONSTRUCTION AND
 CONSTRUCTION-RELATED STRUCTURES, SUCH AS TEMPORARY
 OFFICES, TRAILERS, SHEDS, AND OTHER FACILITIES FOR THE
 STORAGE OF TOOLS AND MATERIALS HAVING COMBUSTIBLE
 CONSTRUCTION OR CONTENTS, SHALL BE IN ACCORDANCE WITH
 TABLE 4.2.1. (NFPA 241).
  
 PROVIDE A PHASED FIRE PROTECTION UTILITY PLAN
 INDICATING THE UNDERGROUND FIRE MAINS, FIRE HYDRANTS
 AND FIRE SPRINKLER SYSTEMS TO BE AFFECTED DURING EACH
 STAGE OF PHASING.
  
 A SUITABLE LOCATION AT THE SITE SHALL BE DESIGNATED AS
 A COMMAND POST AND PROVIDED WITH PLANS, EMERGENCY
 INFORMATION, KEYS, COMMUNICATIONS, AND EQUIPMENT, AS
 NEEDED.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241 - STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 TRASH CHUTES, WHERE PROVIDED, SHALL COMPLY WITH THE
 FOLLOWING: A TRASH CHUTE SAFETY PLAN SHALL BE SUBMITTED
 TO AND APPROVED BY THE AUTHORITY HAVING
 JURISDICTION.TRASH CHUTES USED ON THE EXTERIOR OF A
 BUILDING SHALL BE OF NONCOMBUSTIBLE CONSTRUCTION, OR
 PROTECTED WITH AUTOMATIC SPRINKLERS AND A LISTED FIRE
 HOSE.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 ***FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.***
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 50 FEET.
  
 FIRE DEPARTMENT ACCESS ROADS/LANES SHALL MAINTAIN AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. FIRE HYDRANTS SHALL BE MAINTAINED WITH
 CLEARANCES OF 7?-6? TO THE FRONT AND SIDES AND 4? TO
 THE BACKSIDE.
  
 RESPONSIBILITY FOR HOT WORK OPERATIONS AND FIRE
 PREVENTION PRECAUTIONS, INCLUDING PERMITS AND FIRE
 WATCHES, SHALL BE IN ACCORDANCE WITH NFPA 51B, STANDARD
 FOR FIRE PREVENTION DURING WELDING, CUTTING, AND OTHER
 HOT WORK.
  
 PER SECTION 7.1 (NFPA 241) AN OVERALL CONSTRUCTION OR
 DEMOLITION FIRE SAFETY PROGRAM SHALL BE DEVELOPED.
 ESSENTIAL ITEMS TO BE EMPHASIZED INCLUDE THE FOLLOWING:
 (1) GOOD HOUSEKEEPING (2) ON-SITE SECURITY (3)
 INSTALLATION OF NEW FIRE PROTECTION SYSTEMS AS
 CONSTRUCTION PROGRESSES (4) PRESERVATION OF EXISTING
 SYSTEMS DURING DEMOLITION (5) DEVELOPMENT OF A PREFIRE
 PLAN WITH THE LOCAL FIRE DEPARTMENT (6) RAPID
 COMMUNICATION (7) CONSIDERATION OF SPECIAL HAZARDS
 RESULTING FROM PREVIOUS OCCUPANCIES (8) PROTECTION OF
 EXISTING STRUCTURES AND EQUIPMENT FROM EXPOSURE FIRES
 RESULTING FROM CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS
  
 THE OWNER SHALL DESIGNATE A PERSON WHO SHALL BE
 RESPONSIBLE FOR THE FIRE PREVENTION PROGRAM AND WHO
 SHALL ENSURE THAT IT IS CARRIED OUT TO COMPLETION. THE
 FIRE PREVENTION PROGRAM MANAGER SHALL HAVE THE
 AUTHORITY TO ENFORCE THE PROVISIONS OF THIS AND OTHER
 APPLICABLE FIRE PROTECTION STANDARDS. THE FIRE
 PREVENTION PROGRAM MANAGER SHALL HAVE KNOWLEDGE OF THE
 APPLICABLE FIRE PROTECTION STANDARDS, AVAILABLE FIRE
 PROTECTION SYSTEMS, AND FIRE INSPECTION PROCEDURES.
 INSPECTION RECORDS SHALL BE AVAILABLE FOR REVIEW BY THE
 AUTHORITY HAVING JURISDICTION. WHERE GUARD SERVICE IS
 PROVIDED, THE FIRE PREVENTION PROGRAM MANAGER SHALL BE
 RESPONSIBLE FOR THE GUARD SERVICE.
  
 FREE ACCESS FROM THE STREET TO FIRE HYDRANTS AND TO
 OUTSIDE CONNECTIONS FOR STANDPIPES, SPRINKLERS, OR
 OTHER FIRE EXTINGUISHING EQUIPMENT, WHETHER PERMANENT
 OR TEMPORARY, SHALL BE PROVIDED AND MAINTAINED AT ALL
 TIMES. PROTECTIVE PEDESTRIAN WALKWAYS SHALL NOT BE
 CONSTRUCTED SO THAT THEY IMPEDE ACCESS TO HYDRANTS. NO
 MATERIAL OR CONSTRUCTION SHALL INTERFERE WITH ACCESS TO
 HYDRANTS, SIAMESE CONNECTIONS, OR FIRE EXTINGUISHING
 EQUIPMENT.
  
 VERTICAL AND HORIZONTAL CUTOFFS SHALL BE RETAINED UNTIL
 RAZING OPERATIONS NECESSITATE THEIR REMOVAL AS
 PERMITTED BY THE AUTHORITY HAVING JURISDICTION. FIRE
 DOORS SHALL BE CLOSED AT THE END OF EACH WORKING DAY.
  
 THE OPERATION OF SPRINKLER CONTROL VALVES SHALL BE
 PERMITTED ONLY BY PROPERLY AUTHORIZED PERSONNEL AND
 SHALL BE ACCOMPANIED BY THE NOTIFICATION OF DESIGNATED
 PARTIES. WHERE THE SPRINKLER PROTECTION IS REGULARLY
 TURNED OFF AND ON TO FACILITATE REMOVAL AND CAPPING OF
 SEGMENTS, THE SPRINKLER CONTROL VALVES SHALL BE CHECKED
 AT THE END OF EACH WORK SHIFT TO ASCERTAIN THAT
 PROTECTION IS IN SERVICE. STANDPIPES SHALL BE
 MAINTAINED IN CONFORMITY WITH THE PROGRESS OF
 DEMOLITION ACTIVITY IN SUCH A MANNER THAT THEY ARE
 ALWAYS READY FOR FIRE DEPARTMENT USE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  