Plan Review Notes
Plan Review Notes For Permit 12080136
Permit Number 12080136
Review Stop B
Sequence Number 3
Notes
Date Text
2012-08-28 10:57:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC 2010 RESIDENTIAL
  
 1. PLAN REVIEW FEES ARE TO BE PAID AT TIME OF
 SUBMITTAL. FAILURE TO PAY PLAN REVIEW FEES WILL RESULT
 IN PERMIT APPLICATION BEING PLACED ON "HOLD" UNTIL FEES
 ARE PAID.
  
 2. SEE PREVIOUS LISTS, RAS 117 CALCULATIONS REQUIRED
 PER GENERAL LIMITATION #7, LAST PAGE OF NOA FOR THE
 BUILT UP ROOF. REGARDING THE SIGNED AND SEALED DOCUMENT
 PREPARED BY RICHARD LOCKSHIN:
  
 A. RAS 117 NOT SUBMITTED. THE DOCUMENT SUBMITTED ARE
 COMPUTER GENERATED WIND PRESSURE CALCULATIONS, NOT
 REQUIRED FOR BUILDINGS UNDER 60' AS THE TABLE IN FBC
 RESIDENTIAL 2010 301.2(2) AND (3) CAN BE USED TO
 DETERMINE WIND DESIGN PRESSURES.
  
 B. SEE PREVIOUS LIST, TRIBUTARY AREA ON PREVIOUS
 ENGINEERING WAS 100SF AND WAS DENIED WITH A REFERENCE
 TO FBC RESIDENTIAL 301.2(2), NOTE (A). THE MOST RECENT
 SIGNED AND SEALED DOCUMENT DATED 8/15 PREPARED BY
 RICHARD LOCKSHIN CALCULATES THE EFFECTIVE WIND AREA AS
 420 AND 200 SF. PLEASE SEE FBC 301.2(2), NOTE (A), AND
 REVISE.
  
 C. INCLUDE A TITLE BLOCK WITH ALL INFORMATION REQUIRED
 BY FS 481.
  
 A CALL HAS BEEN PLACED TO THE ARCHITECT IN AN EFFORT TO
 GET THIS ISSUE RESOLVED.
  
  
  