Plan Review Notes For Permit 12080136 |
Permit Number |
12080136 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-08-28 10:57:09 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC 2010 RESIDENTIAL | | | | 1. PLAN REVIEW FEES ARE TO BE PAID AT TIME OF | | SUBMITTAL. FAILURE TO PAY PLAN REVIEW FEES WILL RESULT | | IN PERMIT APPLICATION BEING PLACED ON "HOLD" UNTIL FEES | | ARE PAID. | | | | 2. SEE PREVIOUS LISTS, RAS 117 CALCULATIONS REQUIRED | | PER GENERAL LIMITATION #7, LAST PAGE OF NOA FOR THE | | BUILT UP ROOF. REGARDING THE SIGNED AND SEALED DOCUMENT | | PREPARED BY RICHARD LOCKSHIN: | | | | A. RAS 117 NOT SUBMITTED. THE DOCUMENT SUBMITTED ARE | | COMPUTER GENERATED WIND PRESSURE CALCULATIONS, NOT | | REQUIRED FOR BUILDINGS UNDER 60' AS THE TABLE IN FBC | | RESIDENTIAL 2010 301.2(2) AND (3) CAN BE USED TO | | DETERMINE WIND DESIGN PRESSURES. | | | | B. SEE PREVIOUS LIST, TRIBUTARY AREA ON PREVIOUS | | ENGINEERING WAS 100SF AND WAS DENIED WITH A REFERENCE | | TO FBC RESIDENTIAL 301.2(2), NOTE (A). THE MOST RECENT | | SIGNED AND SEALED DOCUMENT DATED 8/15 PREPARED BY | | RICHARD LOCKSHIN CALCULATES THE EFFECTIVE WIND AREA AS | | 420 AND 200 SF. PLEASE SEE FBC 301.2(2), NOTE (A), AND | | REVISE. | | | | C. INCLUDE A TITLE BLOCK WITH ALL INFORMATION REQUIRED | | BY FS 481. | | | | A CALL HAS BEEN PLACED TO THE ARCHITECT IN AN EFFORT TO | | GET THIS ISSUE RESOLVED. | | | | | | |
|